Basic Specifications |
Power quality measurement standard compliance |
IEEE 1159, IEC 61000-4-30 Ed. 2 Class A |
Maximum recording period |
1 month (with repeat function on: 55 weeks) |
Maximum number of recordable events |
1,000 (with repeat function on: 55,000) |
Interfaces |
SD card slot (for writing data to an SD memory card), LAN (for remote operation and downloading of recorded data), USB (for downloading of recorded data), RS-232C (for printer and GPS connectivity) |
Display |
6.5-inch TFT color LCD (640×480 dots) |
Power supply |
AC ADAPTER Z1002 (12V DC, Rated power supply 100V AC to 24 V AC, 50/60Hz)
BATTERY PACK Z1003 (Ni-MH 7.2V DC 4500mAh) |
Dimensions, mass |
300mm(11.81in)W × 211mm(8.31in)H × 68mm(2.68in)D (excluding protrusions), 2.6kg(91.7oz) (including battery pack) |
Supplied Accessories |
Instruction manual ×1, Measurement guide ×1, VOLTAGE CORD L1000×1 set, Spiral Tube×1, Input Cable Labels ×1, AC ADAPTER Z1002 ×1, Strap ×1, USB cable (1m 3.28ft length) ×1, BATTERY PACK Z1003 ×1, SD MEMORY CARD 2GB Z4001 ×1 |
Measurement Specifications |
Voltage items |
RMS voltage, waveform peak, harmonic, harmonic phase angle, inter-harmonics, high-order harmonic component, total harmonic distortion factor, unbalance factor (negative-phase and zero-phase), DC voltage, frequency V10 |
Current items |
RMS current, waveform peak, harmonic, harmonic phase angle, inter-harmonics, high-order harmonic component, total harmonic distortion factor, unbalance factor (negative-phase and zero-phase), DC current, K factor |
Power items |
Active power, reactive power, apparent power, harmonic power, harmonic voltage-current phase difference, active integral power, reactive integral power, power factor |
Transients, swells, dips, interruptions, frequency, rush current, voltage waveform comparison, timer, external, and other combinations of the time series item events listed above. |
Input Specifications |
Measurement line |
1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire, 3-phase 4-wire
Plus 1 channel in addition to the above measurement lines |
Measurement frequency |
Basic frequency: 50/60/400 Hz
Transient overvoltage: 2 MHz sampling |
Harmonic measurement |
Orders 0 (DC) to 50 (2.5 kHz or 3 kHz) |
Voltage measurement range |
Voltage measurement: 600.00 Vrm
Transient overvoltage measurement: ±6.0000 kV peak |
Current measurement range |
Load current measurement |
With 9694 sensor: 5.0000/50.000 Arms
With 9660 sensor: 50.000/100.00 Arms
With 9661 sensor: 50.000/500.00 Arms
With 9667 sensor: 50.000/500.00 A, 500.00 A/5.0000 kArms
With 9669 sensor: 100.00 A/1.0000 kArms |
Leak current measurement |
With 9675/9657-10 sensor: 500.00 mA/5.0000 Arms |
Measurement accuracy (50 Hz/60 Hz measurement) |
RMS voltage |
±0.1% rdg. |
RMS current |
±0.2% rdg. ±0.1% f.s. + current sensor accuracy |
Active power |
±0.2% rdg. ±0.1% f.s. + current sensor accuracy |