Electrical Specifications |
Operating Range |
1 to 1200A |
Operating Range |
Current Range |
1 to 1000AAC |
Frequency Range |
30Hz to 5kHz; current derating above 1kHz using the formula: (1000A * ) / F (in kHz) |
Common Mode Voltage |
600VAC |
Crest Factor |
£6 |
Current Overload |
1200A for 30 min ON, 15 min OFF |
Current Overload |
Range Value |
250:5 - 20mA/A, 500:5 - 10mA/A, 1000:5 - 5mA/A |
Overload |
300A for 30 min ON, 15 min OFF, 600A for 30 min ON, 15 min OFF 1200A for 30 min ON, 15 min OFF |
Load Impedance |
0.4W max |
Open Secondary Voltage |
<25V by limiting circuit |
Reference Conditions |
23°C ±3°K, 20 to 75% RH, 48 to 65Hz, external magnetic field <40A/m, no DC component, no external current carrying conductor, test sample centered, load impedance 0.2W @ lead <40mW; 0.1W for 250A range |
Ratio |
Ratio |
250:5, 500:5, 1000:5 |
Working Voltage |
600V, Cat. III |
Influence of Adjacent Conductor |
Influence of Adjacent Conductor |
<1mA/AAC |
Influence of Conductor Position |
Influence of Conductor Position |
0.2% of Reading @ 50/60Hz |
Influence of Frequency |
Range |
250:5, 500:5, 1000:5 |
Range Value |
65 to 100Hz / 100 to 1000Hz / 65 to 100Hz / 100 to 1000Hz / 65 to 100Hz / 100 to 1000Hz |
Influence of Frequency |
< 1% of Reading, < 5% of Reading, < 1% of Reading, < 0.5% of Reading, < 1% of Reading |
Influence of Humidity |
Range Value |
250:5, 500:5, 1000:5 |
Influence of Humidity |
< 0.6% & < 2°, < 0.4% & < 0.6°, < 0.2% & < 0.2° |
Output Signal |
Output Signal |
5mA, 10mA, 20mAAC/AAC (5AAC at 250, 500 or 1000A) |
Accuracy |
Current Range |
20mA/A, 10mA/A, 5mA/A |
Ratio |
250:5, 500:5, 1000:5 |
Accuracy |
Per IEC 185-26-27 |
Mechanical Specifications |
Altitude |
Operating: 0 to 2000m; Non-operating: 0 to 12km |
Colors |
Dark gray handles with red jaws |
Dimensions |
4.37 x 8.50 x 1.77" (111 x 216 x 45mm) |
Drop Test |
1m (IEC 68-2-32) |
Jaw Opening |
2.25" (57mm) max |
Material |
Handles: Polycarbonate +ABS Gray: UL 94 V0; Jaws: Polycarbonate, Red: UL 94 V0 |
Maximum Bus Bar Size |
1.95 x 0.19" (50 x 5mm) |
Maximum Cable Diameter |
2.05" (52mm) |
Mechanical Shock |
100g (IEC 68-2-27) |
Operating Temperature |
14° to 122°F (-10° to 50°C) |
Operating Relative Humidity |
0 to 85% @ 35°C |
Output |
Two standard safety banana jacks (4mm) |
Protection Index (IP) |
IP 40 (IEC 529) |
Impact Test |
IK04 0.5 J EN50102 |
Storage Temperature |
-4° to 158°F (-20° to 70°C) |
Vibration |
Test per IEC 68-2-6 |
Vibration |
Range Value |
5 to 15Hz / 15 to 25Hz / 25 to 55Hz |
Vibration |
Amplitude: 0.15 mm per IEC 68-2-6, Amplitude: 1 mm per IEC 68-2-6 Amplitude : 0.25 mm per IEC 68-2-6 |
Weight |
1.21 lbs (550g) |
External Influences |
Influence of Temperature |
<0.13% per 10K° |
Safety Reference Specifications |
Safety Ratings |
EN 61010-2-32 |
Agency Approvals |
CE Mark |