AC current |
Range |
Resolution |
Accuracy |
Frequency Response |
Overload Protection |
400 A
1000 A
1500 A
400 A
1000 A
1500 A |
0.1 A
1 A
1 A
0.1 A
1 A
1 A |
±(1.5% reading + 5 digits)*
±(1.9% reading + 7 digits)
±(2.5% reading + 7 digits)
±(1.9% reading + 5 digits)*
±(2.5% reading + 7 digits)
±(3.0% reading + 7 digits) |
50 Hz ~ 60 Hz
50 Hz ~ 60 Hz
50 Hz ~ 60 Hz
61Hz ~ 400 Hz
61 Hz ~ 200Hz
61 Hz ~ 200 Hz |
1500 A rms
1500 A rms
1500 A rms
1500 A rms
1500 A rms
1500 A rms |
AC Conversion Type |
* add 2 digits to accuracy when reading less 15% of full scale.
AC Conversions are ac-coupled, true rms responding, calibrated to the rms value of a sine wave input. Accuracies
are given for sine wave at full scale and non-sine wave below half scale. For non-sine wave add the following Crest
Factor corrections:
For Crest Factor of 1.4 to 2.0, add 1.0% to accuracy.
For Crest Factor of 2.0 to 2.5, add 2.5% to accuracy.
For Crest Factor of 2.5 to 3.0, add 4.0% to accuracy. |
Max.CF |
2 @ 600A
1.5 @ 1500A |
DC current |
Range |
Resolution |
Accuracy |
Over voltage protection |
400 A
1000 A
1500 A
Position Error: Add |
0.1 A
1 A
1 A
±1% of LCD reading |
±(1.0% reading + 3 digits)
±(1.9% reading + 7 digits)
±(2.5% reading + 7 digits) |
AC 1000 A for 1 min
AC 1000 A for 1 min
AC 1000 A for 1 min |
AC voltage (auto-ranging) |
Range |
Resolution |
Accuracy |
Over voltage protection |
400 V
750 V |
100 mV
1 V |
±(1.0% reading + 5 digits)
50 Hz ~ 500 Hz*
±(1.0% reading + 5 digits)
50 Hz ~ 500 Hz*
(* add 2 digits to accuracy when reading less 15% of full scale.) |
750 V rms
750 V rms |
Input Impedance |
≥1 MΩ// less than 100pF |
AC Conversion Type |
AC Conversions are ac-coupled, true rms responding, calibrated to the rms value of a sine wave input. Accuracies are given
for sine wave at full scale and non-sine wave below half scale.
For non-sine wave add the following Crest Factor corrections:
For Crest Factor of 1.4 to 2.0, add 1.0% to accuracy.
For Crest Factor of 2.0 to 2.5, add 2.5% to accuracy.
For Crest Factor of 2.5 to 3.0, add 4.0% to accuracy.
Max.CF: 2 @ 600V, 1.5 @ 750V |
DC voltage (auto-ranging) |
Range |
Resolution |
Accuracy |
Over voltage protection |
400 V
1000 V |
100 mV
1 V |
±(0.7% reading + 2 digits)
±(0.7% reading + 2 digits) |
1000 V rms
1000 V rms |
Input impedance |
≥ 1 MΩ |
Resistance and continuity |
Range |
Resolution |
Accuracy |
Over voltage protection |
0 – 400 Ω |
100 mΩ |
±(1.0% reading + 3 digits) |
600 V rms |
Continuity check |
Buzzer sounds when resistance< 30 Ω |
Frequency |
Range |
Resolution |
Accuracy |
Over voltage protection |
20 – 400 Hz |
1 Hz |
±(0.1% reading + 2 digits) |
AC /DC 1000 A for 1 min |
Sensitivity |
3 A rms for < 400 Hz |
Peak Hold |
±(3% reading +10 digits)
* >750 V Unspecified.
* >800 A Unspecified. |
Min/Max Hold |
Add ± 15 dgt to accuracy for ACA and DCA. |
LCD |
Display: 3 3/4 digit large scale readout
Count: 4000
Overrange: “OL” |
Power supply |
1 x PP3 MN1604 6LR61 alkaline cell
Battery life: 100 hours |
Operating temperature range and humidity |
0 °C - 30 °C (≤ 80% RH)
30 °C - 40 °C (≤ 75% RH)
40 °C - 50 °C (≤ 45% RH) |
Conductor size |
Maximum conductor size: 51 mm |
Safety |
IEC61010-1 CAT IV 600 V
For use on uninsulated conductors |
EMC |
EN61326-1 |
Pollution degree |
2 |
Storage temperature range |
-20°C - + 60°C 0 to 80% RH (Battery removed) |
Dimensions |
105 mm (W) x 275 mm (L) x 48 (H) |
Weight |
524 g including battery |