(4) Differential Voltage: 16 bit resolution |
• 0-1000Vrms, AC/DC, +/- 0.1% reading +/- 0.05% FS
• IEC 61000-4-30 Class A Ed 3: 60-1000Vrms, ±0.1 % of Udin, range of 10% ~ 150% of Udin
• Transients - 0-1414Vpk, +/- .2% of Udin |
(4) Current: 512 samples/cycle, 16 bit resolution |
• Range (rms) probe dependent, AC/DC, +/- 0.1% reading +/- 0.05% FS
• Transients - Range probe dependent |
Frequency: 10 sec window |
• 16-25Hz, 42.5-69Hz, +/- 0.01Hz |
Distortion - 200ms, 3 sec, 10 min windows |
• Vthd: 0-100%, +/- 5% for V>=1% Vnom,
• V Ind Harm: DC, 2-127, +/- 5% for V>=1% Vnom
• Ithd: 0-100%, +/- 5% for I>=1% Inom,
• I Ind Harm: DC, 2-63, +/- 5% for I>=1% Inom |
Misc. |
• Pst - 10 minutes: 0.2-10, +/- 0.05 @ Pst=1
• Plt - 2 hours: 0.2-10, +/- 0.05 @ Pst=1 |
Dranetz HDPQ Visa |
Size: (10"w x 8"h x 2.75"d), (25.4cm x 20.3cm x 7.0cm)
Weight: 4.2lbs, 2kg
Operating temperature: 0 to 50 deg C ( 32 to 122 deg F)
Storage temperature: -20 to 60 deg C (-4 to 131 deg F)
Humidity: 10-90% non condensing
AC Adapter (12V): 100-240Vac 50/60Hz |
Clock accuracy and resolution |
Internal: +/- 1 sec/day at 25 deg C
NTP: +/-10 msec
GPS: +/-1 msec |
Battery capacity and charge time: |
• Dranetz HDPQ Visa Plus: 3 hours run time on full charge, 3 hours charge time |
Memory size: |
4GB |
Display: |
7" WVGA color graphic, Icon based touch LCD, LED Backlit |
Languages: |
English, German, Spanish, French, Italian, Swedish, Finnish, Polish, Chinese (traditional and simplified), Thai, Korean |
Communications |
Ethernet
Bluetooth (optional)
USB On the Go (OTG)
VNC remote control
Android & Apple Apps |
Power Quality |
IEC 61000-4-30 Class A Edition 3
IEEE 1159: 2009 |
Power |
IEEE 1459: 2000 |
Harmonics |
IEC 61000-4-7 Class 1: Edition 2 (2008)
IEEE 519: 2014 |
Voltage Flicker |
IEC 61000-4-15: Edition 2 (2010)
IEEE 1453: 2011 |
Compliance/Testing |
EN 50160: 2010 |
Ease of Use Features |
Automatic Setups - Start monitoring in seconds!
Pre-programmed monitoring modes - Pre-configured setups for various applications
Dashboards - Power Quality, Demand & Energy - Immediately know when events have been recorded
Simultaneous Power Quality, Demand & Energy monitoring
Mini-Report - Take screen snapshots that can be uploaded to your computer and included in reports, attached to emails, etc. |
Calculated Parameters |
Power/Energy - 1 Second sampling
Real Power (W) - P: meets 0.2S requirements, range probe dependent
Apparent Power (VA) - S: meets 0.2S requirements, range probe dependent
Reactive Power (var) - Q: meets 0.2S requirements, range probe dependent
Power Factor (W/VA) -"true" -1 to 0 to 1
Displacement PF -1 to 0 to 1
Demand (in W): meets 0.2S requirements, range probe dependent
Energy (in Wh): meets 0.2S requirements, range probe dependent |