| Power supply |
100-240VAC 50/60Hz |
| Allowable voltage range |
90 to 110% of rated voltage |
| Power Consumption |
Max. 8VA |
| Display Method |
11 segments (PV: white, SV: green), other display (yellow) with LCD method*1 |
| Character size |
PV(W×H) |
6.9×15.3mm |
| SV(W×H) |
4.1×9.2mm |
| Input type |
RTD |
DPt100Ω, Cu50Ω (permissible line resistance max. 5Ω) |
| TC |
K(CA), J(IC), L(IC), T(CC), R(PR), S(PR) |
| Display Accuracy*2 |
RTD |
- At room temperature (23°C±5°C): (PV ±0.3% or ±1°C, select the higher one) ±1digit
- Out of room temperature: (PV ±0.5% or ±2°C, select the higher one) ±1digit
|
| TC |
| Control Output |
Relay |
250VAC 3A 1a |
| SSR |
Max. 12VDC ± 2V 20mA |
| Current |
DC4-20mA or DC0-20mA (load resistance max. 500Ω) |
| Option Output |
Alarm output |
AL1, AL2 Relay: 250VAC 3A 1a |
| Trans. output |
DC4-20mA (load resistance max. 500Ω, output accuracy: ±0.3%F.S.) |
| Com. output |
RS485 Communication output (Modbus RTU method) |
| Control Method |
ON/OFF control, P, PI, PD, PID control |
| Hysteresis |
1 to 100°C/°F (0.1 to 50.0°C/°F) variable |
| Proportional Band (P) |
0.1 to 999.9°C/°F |
| Integral Time (I) |
0 to 9999 sec. |
| Derivative Time (D) |
0 to 9999 sec. |
| Control Period (T) |
0.5 to 120.0 sec. |
| Manual Reset |
0.0 to 100.0% |
| Sampling period |
50ms |
| Dielectric strength |
3,000VAC 50/60Hz for 1 min. (between all terminals and case) |
| Vibration |
0.75mm amplitude at frequency 5 to 55Hz (for 1 min.)in each X, Y, Z direction for 2 hours |
| Relay Life Cycle |
Mechanical |
OUT, AL1/2: Min. 5,000,000 operations |
| Electrical |
OUT, AL1/2: Min. 200,000 (250VAC 3A resistance load) |
| Insulation Resistance |
Min. 100MΩ (at 500VDC megger) |
| Noise Resistance |
Square shaped noise by noise simulator (pulse width 1µs) ±2kV R-phase, S-phase |
| Memory retention |
Approx. 10 years (non-volatile semiconductor memory type) |
| Environment |
Ambient Temperature |
-10 to 50°C, storage: -20 to 60°C |
| Ambient Humidity |
35 to 85%RH, storage: 35 to 85%RH |
| Protection structure |
IP50 (front panel, IEC standards) |
| Insulation Type |
Double insulation or reinforced insulation
(dielectric strength between all terminals and case: 3kV) |
| Weight*3 |
Approx. 135.2g (approx. 85.2g) |
*1: When using the unit at low temperature (below 0°C), display cycle is slow. Control output operates normally.
*2: At room temperature(23°C±5°C)TC R(PR), S(PR), below 200°C: (PV ±0.5% or ±3°C, select the higher one) ±1 digit, over 200°C: (PV ±0.5% or ±2°C, select the higher one) ±1 digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2°C, select the higher one) ±1 digit
Out of room temperature range
TC R(PR), S(PR): (PV ±1.0% or ±5°C,select the higher one) ±1 digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3°C, select the higher one) ±1 digit
*3: The weight includes packaging. The weight in parentheses is for unit only.
Environment resistance is rated at no freezing or condensation. |
| Type |
LCD display |
| Power Supply |
110 - 220 VAC |
| Dimensions |
48 x 48 mm |
| Control Output |
Current output (DC4- 20 mA)+SSR voltage output |