Power supply |
100-240VAC 50/60Hz |
Allowable voltage range |
90 to 110% of rated voltage |
Power Consumption |
Max. 8VA |
Display Method |
11 segments (PV: white, SV: green), other display (yellow) with LCD method*1 |
Character size |
PV(W×H) |
6.9×15.3mm |
SV(W×H) |
4.1×9.2mm |
Input type |
RTD |
DPt100Ω, Cu50Ω (permissible line resistance max. 5Ω) |
TC |
K(CA), J(IC), L(IC), T(CC), R(PR), S(PR) |
Display Accuracy*2 |
RTD |
- At room temperature (23°C±5°C): (PV ±0.3% or ±1°C, select the higher one) ±1digit
- Out of room temperature: (PV ±0.5% or ±2°C, select the higher one) ±1digit
|
TC |
Control Output |
Relay |
250VAC 3A 1a |
SSR |
Max. 12VDC ± 2V 20mA |
Current |
DC4-20mA or DC0-20mA (load resistance max. 500Ω) |
Option Output |
Alarm output |
AL1, AL2 Relay: 250VAC 3A 1a |
Trans. output |
DC4-20mA (load resistance max. 500Ω, output accuracy: ±0.3%F.S.) |
Com. output |
RS485 Communication output (Modbus RTU method) |
Control Method |
ON/OFF control, P, PI, PD, PID control |
Hysteresis |
1 to 100°C/°F (0.1 to 50.0°C/°F) variable |
Proportional Band (P) |
0.1 to 999.9°C/°F |
Integral Time (I) |
0 to 9999 sec. |
Derivative Time (D) |
0 to 9999 sec. |
Control Period (T) |
0.5 to 120.0 sec. |
Manual Reset |
0.0 to 100.0% |
Sampling period |
50ms |
Dielectric strength |
3,000VAC 50/60Hz for 1 min. (between all terminals and case) |
Vibration |
0.75mm amplitude at frequency 5 to 55Hz (for 1 min.)in each X, Y, Z direction for 2 hours |
Relay Life Cycle |
Mechanical |
OUT, AL1/2: Min. 5,000,000 operations |
Electrical |
OUT, AL1/2: Min. 200,000 (250VAC 3A resistance load) |
Insulation Resistance |
Min. 100MΩ (at 500VDC megger) |
Noise Resistance |
Square shaped noise by noise simulator (pulse width 1µs) ±2kV R-phase, S-phase |
Memory retention |
Approx. 10 years (non-volatile semiconductor memory type) |
Environment |
Ambient Temperature |
-10 to 50°C, storage: -20 to 60°C |
Ambient Humidity |
35 to 85%RH, storage: 35 to 85%RH |
Protection structure |
IP50 (front panel, IEC standards) |
Insulation Type |
Double insulation or reinforced insulation
(dielectric strength between all terminals and case: 3kV) |
Weight*3 |
Approx. 135.2g (approx. 85.2g) |
*1: When using the unit at low temperature (below 0°C), display cycle is slow. Control output operates normally.
*2: At room temperature(23°C±5°C)TC R(PR), S(PR), below 200°C: (PV ±0.5% or ±3°C, select the higher one) ±1 digit, over 200°C: (PV ±0.5% or ±2°C, select the higher one) ±1 digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2°C, select the higher one) ±1 digit
Out of room temperature range
TC R(PR), S(PR): (PV ±1.0% or ±5°C,select the higher one) ±1 digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3°C, select the higher one) ±1 digit
*3: The weight includes packaging. The weight in parentheses is for unit only.
Environment resistance is rated at no freezing or condensation. |
Type |
LCD display |
Power Supply |
110 - 220 VAC |
Dimensions |
48 x 48 mm |
Control Output |
Current output (DC4- 20 mA)+SSR voltage output |