General Specifications |
Model |
TOS |
TOM |
TOL |
Power supply |
100-240VAC 50/60Hz |
110/220VAC 50/60Hz |
Allowable voltage range |
90 to 110% of rated voltage |
Power consumption |
Max. 2.2VA |
Max.3VA |
Display method |
LED ON |
LED ON/OFF |
Setting type |
Dial setting |
Setting accuracy |
F.S. ±2% |
Sensor input |
Thermocouples: K (CA), J (IC) / RTD: DPt100Ω |
Input line resistance |
Thermocouples: Max. 100Ω, RTD: Allowable line resistance max. 5Ω per a wire |
Control method |
ON/OFF |
Hysteresis: F.S. 0.5% ±0.2% fixed |
Proportional |
Proportional band: F.S. 3% fixed, Period: 20sec. fixed |
Control output |
Relay output: 250VAC 2A 1c
SSR drive output: 12VDC ±3V Load 20mA Max |
Relay output: 250VAC 3A 1c
SSR drive output: 12VDC ±3V 20mA Max. |
Self-diagnosis |
Built-in burn out function (cut off output when sensor is disconnected) |
Insulation resistance |
Min. 100MΩ (at 500VDC megger) |
Dielectric strength |
2,000VAC 50/60Hz for 1 min. |
Noise resistance |
±1kV the square wave noise (pulse width: 1㎲) by the noise simulator |
Vibration |
Mechanical |
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min.) in each X, Y, Z direction for 1 hour |
Malfunction |
0.5mm amplitude at frequency of 10 to 55Hz (for 1 min.) in each X, Y, Z direction for 10 min |
Shock |
Mechanical |
300m/s² (approx. 30G) in each X, Y, Z direction for 3 times |
Malfunction |
100m/s² (approx. 10G) in each X, Y, Z direction for 3 times |
Relay life cycle |
Mechanical |
Min. 10,000,000 operations |
Malfunction |
Min. 100,000 operations (250VAC 3A at resistive load ) |
Environment |
Ambient temperature |
-10 to 50℃, storage: -25 to 65℃ |
Ambient humidity |
35 to 85%RH, storage: 35 to 85%RH |
Approval |
|
--- |
--- |
Unit weight |
Approx. 104g |
Approx. 419g |
Approx. 426g |
※F.S. is same with sensor measuring temperature range. E.g.) In case of using temperature is from 0 to 800℃, Full scale is "800".
※Environment resistance is rated at no freezing or condensation. |