Model: TOL Series Specifications |
Description |
Temperature control |
Power supply |
110/220 VAC 50/60Hz |
Allowable voltage range |
90 to 100% of rated voltage |
Power consumption |
3VA |
Dsplay method |
LED ON/OFF |
Setting type |
Dial setting |
Setting accuracy |
F.S.±2% |
Sensor input |
Thermocouples: K (CA), J (IC) / RTD: DPt100Ω |
Input line resistance |
Thermocouples: Max. 100Ω, RTD: Allowable line resistance max. 5Ω per a wire |
Control method |
ON/OFF |
Hysteresis: F.S. 0.5% ±0.2% fixed |
Proportional |
Proportional band: F.S. 3% fixed, Period: 20 sec. fixed |
Control output |
Relay output: 250BAC 2A 1c, SSR drive output: 12VDC ±3V 20mA Max. |
Self-diagnosis |
Built-in burn out function (cut off output when sensor is disconnected) |
Insulation resistance |
Min. 100MΩ (at 500VDC megger) |
Dielectric strength |
2,000VAC 50/60Hz for 1 min. |
Noise resistance |
± 1kV the square wave noise (pulse width 1us) by the noise simulator |
Vibration |
Mechanical |
0.75 mm amplitude at frequency of 10 to 55 Hz (for 1 min.) in each X, Y, Z direction fo 1 hour. |
Malfunction |
0.5mm amplitude at frequency of 10 to 55 Hz (for 1 min.) in each X, Y, Z direction fo 10 hour. |
Shock |
Mechanical |
300m/s2 (approx. 30G) in each X,Y,Z direction for 3 times |
Malfunction |
100m/s2 (approx. 30G) in each X,Y,Z direction for 3 times |
Relay life cycle |
Mechanical |
Min. 10.000, 000 operations |
Electrical |
Min. 100,000 operations (250VAC 3A at resistive load) |
Unit weight |
Approx. 426g |