Power supply |
100-240VAC 50/60Hz |
Allowable voltage range |
90 to 110 of rated voltage |
Power consumption |
Max. 5VA |
Display method |
7 Segment (PV: green, SV: red) LED method |
Character size (W×H) |
8×10mm |
Input Type |
RTD |
DPt100Ω [Allowable line resistance is max. 5Ω per a wire] |
Thermocouple |
K (CA), J (IC) [Tolerance outer resistance is max. 100Ω] |
Control Output |
Relay |
250VAC 3A 1a |
--- |
--- |
--- |
SSR |
--- |
12VDC ±3V 30mA Max. |
--- |
--- |
Current |
--- |
--- |
DC4-20mA (max. load 600Ω) |
--- |
Transmission |
--- |
--- |
--- |
DC4-20mA (max. load 600Ω) |
Sub output |
- Event 1 output: Relay output (250VAC 0.5A 1a) • Event 2 output: OK monitoring display by LED
|
Control method |
ON/OFF control, P, PI, PD, PIDF, PIDS control |
Setting type |
Front push buttons |
Display accuracy |
F.S ± 0.3% or 3°C, select the higher one |
Hysteresis |
1 to 100°C (0.1 to 100.0°C) variable (at ON/OFF control) |
Proportional band (P) |
0.0 to 100.0% |
Integral time (I) |
0 to 3600 sec. |
Derivative time (D) |
0 to 3600 sec. |
Control cycle (T) |
1 to 120 sec. |
Sampling period |
0.5 sec. |
Dielectric strength |
2,000VAC 50/60Hz for 1 minute (Between input and power terminal) |
Vibration |
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min.) in each X, Y, Z direction for 2 hours |
Relay Life Cycle |
Main Output |
Mechanical: Min. 10,000,000, Electrical: Min. 100,000 (250VAC 3A resistive load) |
Sub Output |
Mechanical: Min. 20,000,000, Electrical: Min. 200,000 (250VAC 0.5A resistive load) |
Insulation Resistance |
Min. 100MΩ (at 500VDC megger) |
Noise Resistance |
±2kV the square wave noise (pulse width: 1µs) by the noise simulator |
Memory Retention |
Approx. 10 years (when using non-volatile semiconductor memory type) |
Environment |
Ambient Temperature |
-10 to 50°C, storage: -20 to 60°C |
Ambient Humidity |
35 to 85%RH, storage: 35 to 85%RH |
Unit Weight |
Approx. 113.5g |