General Specifications |
Dielectric strength (Vrms) |
24-240VAC~rated load current 15A/30A
: 2500VAC 50/60Hz 1 min (input-output, input/output-case) |
24-240VAC~rated load current 50A/75A,
48-480VAC~ rated load current 15A/30A/40A/50A/75A
: 4000VAC 50/60Hz 1 min (input-output, input/output-case) |
Insulation resistance |
Over 100MΩ (at 500VDC megger) (input-output, input/output-case) |
Indicator |
Input indicator: Green LED, alarm output indicator: Red LED |
Vibration |
Mechanical |
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour |
Malfunction |
0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min |
Shock |
Mechanical |
300m/s² (approx. 30G) in each X, Y, Z direction for 3 times |
Malfunction |
100m/s² (approx. 30G) in each X, Y, Z direction for 3 times |
Environment |
Ambient temp |
-30 to 80℃ (in case of the rated input voltage 90-240VACЖ: -30 to 70℃), storage: -30 to 100℃ (The rated load current capacity is different depending on ambient temperature. Refer to ' SSR Derating Curve'.) |
Ambient humi |
45 to 85%RH, storage: 45 to 85%RH |
Input terminal connection, alarm output terminal connection |
Min. 1×0.5mm2 (1×AWG20), max. 1×1.5mm2 (1×AWG16) or 2×1.5mm2 (2×AWG16) |
Output terminal connection |
Min. 1×1.5mm2 (1×AWG16), max. 1×16mm2 (1×AWG6) or 2×6mm2 (2×AWG10) ※Use wires compliant with load current capacity to connect to the terminal. |
Input terminal fixed torque |
0.75 to 0.95N·m |
Output terminal fixed torque |
1.6 to 2.2N·m |
Weight※1 |
Detachable heatsink type: Approx. 365g (approx. 275g)
Integrated heatsink type - Rated load current 15A/30A/40A
: Approx. 896g (approx. 686g) - Rated load current 50A
: Approx. 1508g (approx. 1268g) - Rated load current 75A: Approx. 2354g (approx. 2064g) |
※1: The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.
※For wiring the terminal, round terminal must be used. |