General Specifications |
Model |
SPB-060-12 |
SPB-060-24 |
SPB-120-24 |
SPB-240-12 |
SPB-240-24 |
SPB-240-48 |
Output power |
60W |
120W |
240W |
Input |
Voltage |
100-240VAC(85-264VAC) |
Frequency |
50/60Hz |
Efficiency*1 |
123 |
123 |
123 |
Power factor*1 |
--- |
Min. 0.9 |
Current consumption*1 |
Max. 1.6A |
Max. 1.9A |
Max. 3.8A |
Power factor correction circuit |
--- |
Built-in |
Output |
Voltage |
12VDC |
24VDC |
12VDC |
24VDC |
48VDC |
Current |
5A |
2.5A |
5A |
20A |
10A |
5A |
Voltage adjustment range*2 |
Max. ±5% |
Input variation*3 |
Max. ±0.5% |
Load variation*1 |
Max. ±1% |
Max. ±1.5% |
Ripple*1 |
Max. ±1% |
Max. ±3% |
Max. 1.5% |
Max. ±1% |
Start-up time*1 |
Max. 600ms |
Max. 1000ms |
Hold time*1 |
Min. 10ms |
Min. 20ms |
Protection |
Inrush current protection |
Max. 25A (100VAC), Max. 40A(240VAC) |
Max. 50A(100VAC), Max. 50A(240VAC) |
Output over current protection*4 |
Min. 105% |
Output over voltage protection |
5A |
30.0V ±10% |
16.0V ±10% |
30.0V ±10% |
58.0V ±10% |
Output short-circuit protection |
Max. 10ms |
Output low-voltage indicate |
9.6V±10% |
9.6V±10% |
10.0V±10% |
20.0V±10% |
43.0V±10% |
Output indicator |
Green LED |
Insulation resistance |
Min. 100MΩ(at 500VDC megger between all input terminals and output terminals) |
Dielectric strength |
3000VAC 50/60Hz for 1 min. (between all input terminals and output terminals) |
1500VAC 50/60Hz for 1 min. (between all input terminals and F.G.) |
Vibration |
0.75 mm amplitude at frequency of 10 to 55 Hz (for 1 min.) in each of X, Y, Z directions for 2 hour |
Shock |
300m/s² (approx. 30G) in each of X, Y, Z directions for 3 times |
EMS |
Conforms to EN61000-6-2 |
EMI |
Conforms to EN61000-6-4 |
Safety |
IEC60950, IEC50178 |
Environment |
Ambient temperature |
-10 to 50 °C , storage: -25 to 65 °C |
Ambient humidity |
25 to 85%RH, storage: 25 to 90%RH |
Protection |
IP20(IEC standard) |
Unit weight*5 |
Approx. 347g(approx. 274g) |
Approx. 570g(approx. 466g) |
Approx. 866g(approx. 736g) |
*1: It is for the rated input voltage 100-240VAC, and 100% load.
*2: Adjusting voltage by the output adjuster (V.ADJ), it is changed the below voltage adjustment range(±5%).
*3: It is for the rated input voltage 100-240VAC(85-264VAC), and 100% load.
*4: It is for the rated input voltage 100-240VAC.
*5: The weight is with packaging and the weight in parentheses is only unit weight.
*Environment is rated at no freezing or condensation. |