Autonics KPN Series General Specifications |
Power supply |
100-240VAC 50/60Hz |
Allowable voltage range |
90 to 110% of rated voltage |
Power consumption |
Max. 15VA |
Display method |
7 Segment(Red, Green), control output Bar graph: Red, Green |
Character size |
PV(W×H) |
7.0×14.6mm |
11.0×22.0mm |
SV(W×H) |
6.0×12.0mm |
6.0×12.0mm |
Input type |
RTD |
JPt 100Ω, DPt 100Ω, DPt 50Ω, Cu 100Ω, Cu 50Ω, Nikel 120Ω(6types) |
TC |
K, J, E, T, L, N, U, R, S, B, C, G, PLII(13types) |
Analog |
Voltage: 0 to 100mV, 0 to 5V, 1 to 5V, 0 to 10V(4types) / Current: 0 to 20mA, 4 to 20mA(2types) |
Display accuracy |
RTD |
• At room temperature(23℃±5℃): (PV ±0.3% or ±1℃, select the bigger one) ±1Digit*1
• Out of range of room temperature: (PV ±0.5% or ±2℃, select the bigger one) ±1Digit |
TC |
Analog |
• At room temperature(23℃±5℃): ±0.3% F.S. ±1Digit,
• Out of range of room temperature: ±0.5% F.S. ±1Digit |
CT input |
±5% F.S. ± 1Digit |
Control output |
Relay |
OUT1, OUT2: 250VAC 5A 1a |
SSR |
11VDC ±2V 20mA Max. |
Current |
DC4-20mA or DC0-20mA (Max. Load 500Ω ) |
Alarm output |
Relay |
AL1, AL2, AL3 Relay: 250VAC 3A 1a |
Option output |
Transmission |
DC4-20mA (Max. Load 500Ω, Output accuracy: ±0.3% F.S. ±1 Digit) |
Communication |
RS485 communication output (Modbus RTU) |
Option input |
CT |
0.0 to 50.0A(Primary heater current value measuring range) *CT ratio = 1/1000 |
Remote SV |
1-5VDC or DC4-20mA (Current input: using external resistance 250Ω) |
Digital input |
• Contact Input: ON-Max. 2KΩ, OFF-Min. 90KΩ
• Non-contact Input: ON-Residual votage max. 1.0V, OFF-leakage current max. 0.1mA |
Control type |
Heating, Cooling |
ON/OFF, P, PI, PD, PID control mode |
Heating & Cooling |
Hysteresis |
• Thermocouple / RTD: 1 to 100°C/°F(0.1 to 100.0°C/°F variable,
• Analog: 1 to 100Digit |
Proportional band(P) |
0.1 to 999.9℃(0.1 to 999.9%) |
Integral time(I) |
0 to 9999 sec. |
Derivative time(D) |
0 to 9999 sec. |
Control period(T) |
0.1 to 120.0 sec(*Relay output and SSR drive output only) |
Manual reset value |
0.0~100.0% |
Sampling period |
50ms |
Dielectric strength |
2000VAC 50/60Hz for 1min.(between power source terminal and input terminal) |
Vibration |
0.75mm amplitude at frequency of 5 to 55Hz (for 1min.) in each X, Y, Z direction for 2 hours |
Relay life cycle |
Mechanical |
Over 10,000,000 times |
Electrical |
Over 100,000 times (250VAC 3A resistance load) |
Insulation resistance |
Over 100MΩ(at 500VDC megger) |
Noise resistance |
Square shaped noise by noise simulator (pulse width 1㎲)±2kV R-phase, S-phase |
Memory retention |
Approx. 10 years(When using non-volatile semiconductor memory type) |
Environment |
Ambient temperature |
-10 to 50°C, storage: -20 to 60°C |
Ambient humidity |
35 to 85%RH, storage: 35 to 85%RH |
Protection |
IP65(Front part) |
Insulation type |
Double insulation or reinforced insulation
(Mark: Dielectric strength between the measuring input part and the power part : 2kV) |
Weight |
Approx. 230g (approx. 160g) |
Approx. 316g (approx. 220g) |
*1: • At room temperature(23°C±5°C)
- TC K, J, T, N, E type, below -100°C / TC L, U, PL°C, RTD Cu50Ω, DPt 50Ω: (PV ±0.3% or ±2°C, select the bigger one)±1Digit
- TC C, G type/TC R, S type, below 200°C: (PV ±0.3% or ±3℃, select the bigger one)±1Digit
- TC B type, below 400℃: There is no accuracy standards.
• Out of range of room temperature
- RTD Cu50Ω, DPt50Ω: (PV ±0.5% or ±3°C, select the bigger one) ±1Digit
- TC R, S, B, C, G: (PV ±0.5% or ±10°C, select the bigger one) ±1Digit
- Others: Below -100°C: Within ±5°C
*The weight is with packaging and the weight in parentheses is only unit weight.
*Environment resistance is rated at no freezing or condensation. |