Model |
Item |
Series |
Monitor Size |
Display Unit |
Color |
Power Supply |
Interface |
GP-S057-S1D1 |
Graphic panel |
S series |
5.7 inch |
STN LCD |
MONO (blue, white) |
24VDC |
Each ports of
RS232C |
Model |
GP-S057-S1D0 |
GP-S057-S1D1 |
Power supply |
24VDC |
Allowable voltage range |
90 to 110% of power supply |
Power consumption |
90 to 110% of power supply |
Display Performance |
LCD type |
5.7 inch STN blue negative |
Resolution |
320×240 dots |
Display area |
119mm×91mm |
Color |
MONO (blue, white) |
LCD view angle |
Top/Bottom/Left/Right within 30°in each direction |
Backlight |
White LED |
Brightness |
Adjustable by software |
Graphic Drawing Performance |
Language *1 |
English, Korean, Japanese, Chinese, Russian, Vietnamese, Portuguese |
Text |
• High resolution display up to 1590 letters (6×8 font)
• 6×8, 8×8 ASCII character, high definition numbers
• 8×16 ASCII characters, 16×16 character by each country (1-8 times bigger for width, 0.5-5 times bigger for height] |
Graphic drawing memory |
512 KB |
Number of user screen |
500 pages |
Touch switch |
Width 16×Height 12 = 192 |
Serial interface |
Each port of RS232C, RS422 (asynchronous method) |
Real-time controller |
RTC embedded |
Battery life cycle |
Approx. 3 years at 25 °C |
Insulated resistance |
Min. 100MΩ (at 500VDC megger) |
Ground |
3rd grounding (max. 100Ω) |
Noise resistance |
± 0.5kV the square wave noise (pulse width: 1μs ) by the noise simulator |
Dielectric strength |
500VAC (50/60Hz) for 1 min. |
Vibration |
Mechanical |
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min.) in each X, Y, Z direction for 1 hour |
Malfunction |
0.5mm amplitude at frequency of 10 to 55Hz (for 1 min.) in each X, Y, Z direction for 10 min. |
Shock |
Mechanical |
300m/s² (approx. 30G) in each X, Y, Z direction for 3 times |
Malfunction |
100m/s² (approx. 10G) in each X, Y, Z direction for 3 times |
Environment |
Ambient temperature |
to 50 °C , storage: -20 to 60 °C |
Ambient humidity |
35 to 85%RH, storage: 35 to 85%RH |
Protection structure |
IP65F (for front panel) |
Accessory |
Fixing bracket: 4EA, Rubber waterproof ring, Battery (included) |
Weight *2 |
Approx. 555g (approx. 376g) |
*1: Language could be added in the future M
*2: The weight includes packaging. The weight in parentheses is for unit only
*Environment resistance is rated at no freezing or condensation |
Functional Description |
Figure display |
Line, rectangle, circle, text, bitmap |
Tags |
Numeral display |
Displays the designated device as numerical value. (decimal, hexadecimal, octal, binary , real number) |
ASCII display |
Displays the designated device value as ASCII character. |
Time display |
Displays current time or date. |
Alarm history |
Registers alarm history. |
Alarm list |
Displays generated (not backed up) alarm. |
Comment display |
Displays the designated comment as device status or value. |
Lamp |
Displays lamp as device status. |
Part display |
Displays the designated parts as device status and value. |
Line graph |
Displays several device values with a graph of broken line. |
Trend graph |
Displays change of device value for time with a graph of broken line. |
Bar graph |
Displays a device value with a bar graph. |
Statistic graph |
Displays a ratio of several device values with pie graph. |
Panel meter |
Displays a device value as panel meter. |
Touch key |
Screen is switched, word/bit device values are set when it touched. |
Numeral input |
Configures user input value in device. |
ASCII input |
Configures user input ASCII code value in device. |
System information function |
Monitors/Controls GP operation from PLC. |
Recipe function |
Reads/Writes several PLC device collectively. |
Security function |
Only acceptable user can observe/operate important data. |
Barcode read function |
Connects barcode reader, read barcode. |
Floating alarm function |
Warning message is floated when alarm is generated. |
Time operation |
Specific bit device is ON/OFF for designated day and time. |
Overlap window |
Available to form dynamically overlapping another base screen on the base one. |
Observe status function |
Changes PLC device status/value of PLC when trigger is generated. |