Yokogawa YPP6300 General Specifications |
Display |
Upper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. Both displays are 6 digits (-99999 to 999999), red LEDs with leading zero blanking. |
Display Intensity |
Eight user selectable intensity levels |
Display Update Rate |
5/second (200 ms) |
Overrange |
Display flashes 999999 |
Underrange |
Display flashes -99999 |
Display Assignment |
The upper and lower displays may be assigned to rate, total, grand total, alternate rate & total, max/min, units (small display only), set points, or Modbus input. |
Front Panel |
NEMA 4X, IP65 |
Programming Methods |
Four front panel buttons, digital inputs, PC and MeterView Pro software, Modbus registers, or cloning using Copy function. |
Noise Filter |
Programmable from 2 to 199 (0 will disable filter) |
Filter Bypass |
Programmable from 0.1 to 99.9% of calibrated span |
Recalibration |
All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months. |
Max/Min Display |
Max (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power to the meter is cycled. |
Password |
Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals.
Pass 1: Allows use of function keys.
Pass 2: Allows use of function keys, digital inputs, and editing set/reset points.
Pass 3: Restricts all programming, function keys, and digital inputs.
Total: Prevents resetting the total manually.
Gtotal: Prevents resetting the grand total manually. |
Non-Volatile Memory |
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost. |
Power Options |
85-265 VAC 50/60 Hz, 90-265 VDC 20 W max, or jumper selectable 12/24 VDC ±10%, 15 W max. |
Fuse |
Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse. |
Isolated Transmitter Power Supply |
Terminals P+ & P-: 24 VDC ± 5% @ 200 mA max (standard), (12/24 VDC powered models rated @ 100 mA max). 5 or 10 VDC @ 50 mA max, selectable with internal jumper J4. |
Normal Rejection Mode |
Greater than 60 dB at 50/60 Hz |
Isolation |
4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply. |
Overvoltage Category |
Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III. |
Environmental |
Operating temperature range: -40 to 65°C.
Storage temperature range: -40 to 85°C.
Relative humidity: 0 to 90% non-condensing. |
Connections |
Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters. |
Enclosure |
1/8 DIN, high impact plastic, UL 94V-0, color: black |
Mounting |
1/8 DIN panel cutout required: 3.622" x 1.772"(92 mm x 45 mm). Two panel mounting bracket assemblies are provided. |
Tightening Torque |
Screw terminal connectors: 5 lb-in (0.56 Nm) |
Overall Dimensions |
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D) |
Weight |
9.5 oz (269 g) |
UL File Number |
UL & c-UL Listed. E348677; 508 Industrial Control Equipment. |
Warranty |
3 years parts & labor |
YPP6200 Analog Inputs |
Inputs |
Field selectable: 0-20, 4-20 mA, ±10 VDC (0-5, 1-5, 0-10 V), Modbus PV (Slave) |
Accuracy |
±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span |
Temperature Drift |
0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient |
Signal Input Conditioning |
Linear, square root, programmable exponent, or round horizontal tank volume calculation. |
Multi-Point Linearization |
2 to 32 points Programmable Exponent: 1.0001 to 2.9999 |
Low-Flow Cutoff |
0-999999 (0 disables cutoff function) |
Decimal Point |
Up to five decimal places or none: D.DDDDD, DD.DDDD,DDD.DDD, DDDD.DD, DDDDD.D, or DDDDDD. |
Calibration Range |
Input Range |
Minimum Span Input 1 & 2 |
4-20 mA |
0.15 mA |
±10 V |
0.10 V |
An Error message will appear if input 1 and input 2 signals are too close together. |
Input Impedance |
Voltage ranges: greater than 1 MΩ. |
Current ranges |
50 - 100 Ω (depending on resettable fuse impedance). |
Input Overload |
Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed. |
YPP6300 Rate Inputs |
Inputs |
Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 kΩ pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7 kΩ pull-up to 5 V @ 40 Hz; coil (sine wave) 40 mVp-p min @ 10 kHz; Modbus PV (Slave) |
Low Voltage Mag Pickup (Isolated) |
Sensitivity: 40 mVp-p to 8 Vp-p |
Minimum Input Frequency |
0.001 Hz - Minimum frequency is dependent on high gate setting. |
Maximum Input Frequency |
30,000 Hz (10,000 for Low Voltage Mag Pickup) |
Input Impedance |
Pulse input: Greater than 300 kΩ @ 1 kHz.
Open collector/switch input: 4.7 kΩ pull-up to 5 V. |
Accuracy |
±0.03% of calibrated span ±1 count |
Display Update Rate |
Total: 10/sec
Rate: 10/sec to 1/1000 sec |
Temperature Drift |
Rate display is not affected by changes in temperature. |
Multi-Point Linearization |
2 to 32 points |
Low-Flow Cutoff |
0-999999 (0 disables cutoff function) |
Decimal Point |
Up to five decimal places or none: D.DDDDD, DD.DDDD, DDD.DDD, DDDD.DD, DDDDD.D, or DDDDDD. |
Calibration |
May be calibrated using K-factor, scale using internal calibration, or calibrate by applying an external calibration signal. |
K-Factor |
Field programmable K-factor converts input pulses to rate in engineering units. May be programmed from 0.00001 to 999,999 pulses/unit. |
Calibration Range |
Input 1 signal may be set anywhere in the range of the meter; input 2 signal may be set anywhere above setting. |
Filter |
Programmable contact de-bounce filter, 40 to 999 Hz maximum input frequency allowed with low speed filter. |
Time Base |
Second, minute, hour, or day |
Low Gate |
0.1-99.9 seconds; this function determines how often the incoming pulses are calulated and the rate display is updated. |
High Gate |
2.0-999.9 seconds; this function determines how long to wait for pulses before the display goes to zero. This function is used to display slow pulse rates.
Note: The combination of the low and high gate functions makes it possible to have a fast display update for fast pulse rates while displaying slow pulse rates, if needed. For example: If the low gate is set to 1.0 second and the high gate to 999.9 second, with a fast pulse rate the display is updated every second; with a slow pulse rate the meter is capable of waiting up to 999.9 seconds before calculating the rate, making it possible to display a very slow rate down to 1 pulse/999.9 second (0.001 pulse/second). |
Rate/Totalizer |
Display Assignment |
The upper and lower displays may be assigned to rate, total, grand total, alternate R & T, units, and set point. |
Rate Display Indication |
0 to 999999, lead zero blanking. “R” LED illuminates while displaying rate. |
Total Display & Total Overflow |
0 to 999,999; automatic lead zero blanking. “T” LED is illuminated while displaying total and “GT” for grand total. Up to 999,999,999 with total-overflow feature. “oF” is displayed to the left of total overflow and ▲ LED is illuminated. |
Alternating Display |
Either display may be programmed to alternate between rate and total or rate and grand total every 10 seconds. |
Total Decimal Point |
Up to five decimal places or none: D.DDDDD, DD.DDDD, DDD.DDD, DDDD.DD, DDDDD.D, or DDDDDD.
Total decimal point is independent of rate decimal point. |
Totalizer |
Calculates total based on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed. |
Total Conversion Factor |
0.00001 to 59,999 |
Totalizer Rollover |
Totalizer rolls over when display exceeds 999,999,999. Relay status reflects the display value. |
Total Overflow Override |
Program total reset for automatic with 0.1 second delay and set point 1 for 999,999 |
Totalizer Presets |
Up to eight, user selectable under Setup menu. Any set point can be assigned to total and may be programmed anywhere in the range of the meter for total alarm indication. |
Programmable Total Reset Delay |
0.1 to 999.9 seconds; applied to the first relay assigned to total or grand total. If the meter is programmed to reset total to zero automatically when the preset is reached, then a delay will occur before the total is reset. |
Total Reset |
Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications. |
Total Reset Password |
Total and grand total passwords may be entered to prevent resetting the total or grand total from the front panel. |
Non-Resettable Total |
The grand total can be programmed as a non-resettable total by entering the password “050873”.
Caution: Once the Grand Total has been programmed as “non-resettable” the feature cannot be disabled. |
Relays |
Rating |
2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads |
Noise Suppression |
Noise suppression is recommended for each relay contact switching inductive loads. |
Relay Assignment |
Relays may be assigned to rate, total, or grand total. Deadband: 0-100% of span, user programmable |
High or Low Alarm |
User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off). |
Relay Operation |
automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), off (disable unused relays), and manual on/off control mode. |
Relay Reset |
User selectable via front panel buttons, digital inputs, or PC.
- Automatic reset only (non-latching), when input passes the reset point or total is reset to zero.
- Automatic + manual reset at any time (non-latching).
- Manual reset only, at any time (latching).
- Manual reset only after alarm condition has cleared (latching).
Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset. |
Deadband |
0-100% of span, user programmable |
Time Delay |
0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay. |
Fail-Safe Operation |
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state. |
Auto Initialization |
When power is applied to the meter, relays will reflect the state of the input to the meter. |
Isolated 4-20 mA Transmitter Output |
Output Source |
Rate/process, total, grand total, max, min, set points 1-8, manual control setting, or Modbus input |
Scaling Range |
1.000 to 23.000 mA for any display range |
Calibration |
Factory calibrated: 4.000 to 20.000 = 4-20 mA output |
Analog Output Programming |
23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break |
Accuracy |
± 0.1% FS ± 0.004 mA |
Temperature Drift |
0.4 μA/°C max from 0 to 65°C ambient, 0.8 μA/°C max from -40 to 0°C ambient.
Note: Analog output drift is separate from input drift. |
Isolated Transmitter Power Supply |
Terminals I+ & R: 24 VDC ± 5% @ 40 mA maximum, may be used to power the 4-20 mA output or other devices. Present on both AC & DC powered units. |
External Loop Power Supply |
35 VDC maximum |
Output Loop Resistance |
Power supply |
Minimum |
Maximum |
24 VDC |
10 Ω |
700 Ω |
35 VDC (external) |
100 Ω |
1200 Ω |
|
Serial Communications |
Protocol |
Modbus® RTU |
Meter Address/Slave ID |
1 - 247 |
Baud Rate |
300 - 19,200 bps |
Transmit Time Delay |
Programmable between 0 and 199 ms or transmitter always on for RS-422 communication |
Data |
8 bit (1 start bit, 1 or 2 stop bits) |
Parity |
Even, odd, or none with 1 or 2 stop bits |
Byte-to-Byte Timeout |
0.01 - 2.54 seconds |
Turn Around Delay |
Less than 2 ms (fixed).
Note: Refer to the YPP6000/YPP7000 Modbus Register Tables located at www.yokogawa-usa.com for details. |
Digital I/O Expansion Module |
Channels |
4 digital inputs & 4 digital outputs per module System: Up to 2 modules for a total of 8 inputs & 8 outputs |
Digital Input Logic |
High: 3 to 5 VDC
Low: 0 to 1.25 VDC |
Digital Output Logic |
High: 3.1 to 3.3 VDC
Low: 0 to 0.4 VDC |
Source Current |
10 mA maximum Sink Current: 1.5 mA minimum |
+5 V Terminal |
To be used as pull-up for digital inputs only. |
4-Relay Expansion Module |
Relays |
Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 watts) @ 125/250 VAC for inductive loads. |