| PV/SP Data display: |
5 digits / 5 digits with LCD display |
| PV inputs: |
2 universal inputs (TCs, RTDs, mV, V) |
| Auxiliary Analog Input: |
1 for secondary PV |
| Control scan period: |
100, 200, 500ms |
| Control loops: |
1 or 2(cascade, dual) |
| Control Modes: |
PRG/RESET, LOCAL, HOLD, ADVANCE |
| Program Pattern: |
30 |
| Number of Patterns: |
300 |
| Number of Segments/ Pattern: |
99 |
| Number of (PV) Events/Segment: |
8 |
| Number of Time Events/Segment: |
16 |
| Number PID Sets: |
8 |
| Current trans input (option): |
2 |
| Ladder Sequence Function (Number of max. steps) |
500 |
| Control Algorithms: |
ON/OFF, 3 position, PID(Continuous,Time-proportional), Heating & Cooling |
| Control Computation: |
Continuous PID control, Time-proportional PID control, Relay ON/OFF control, Heating/Cooling control, Target setpoint , PID parameter, Auto-tuning, "SUPER" function, "SUPER2" function, Preset output function and Control cycle time |
| Operation Mode switching: |
Start of program operation (PROG)
Stop of program operation (RESET)
Start of local-mode operation (LOCAL)
Start of remote-mode operation (REM)
Pause/cancel release of program operation (HOLD)
Advance of segment (ADV)
Automatic (AUTO)/Manual (MAN) switching
Local (LSP)/CAS switching when in cascade control |
| Parameters: |
Segment PID
(Measured input zone, PID, Target setpoint zone, PID, Reached target setpoint zone, PID Local, PID Reference deviation) Proportional band, Integral time, Derivative time, ON/OFF control hysteresis
(one or two hysteresis points), Preset output value, Output limiter, Rate of change limiter of output, Dead band of heating/cooling control, Dead band of position-proportional control, Shutdown function |
| Standard (Max.) |
1(Std) 4(Max) |
| Standard (Max.) |
2(Std) 3(Max) |
| Auxiliary Analog Output |
1 point, 2 points when MV is relay output (4-20mA) |
| Control Outputs (MV) |
Select from 2 sets of Relays, Voltage Pulses or 4 to 20mA |
| Standard (Max.) |
8(Std) 18(Max) |
| Number: |
8(Std) 9(Max) |
| Number: |
1 |
| Standard (Max.) |
2(Std) 3(Max) |
| Auxiliary Analog Output |
1 point, 2 points when MV is relay output (4-20mA) |
| Number: |
1 or 3 |
| Type: |
PV, SP, OUT, etc |
| Number: |
1 point |
| Type: |
1 to 5 V, etc
Only 1 input can be changed to universal input when specified the /DR option |
| Number: |
1 point |
| Type: |
21.6 to 28.0 VDC |
| Number: |
1 |
| Type: |
RS-485, Ethernet, PROFIBUS-DP, CC-Link, DeviceNet |
| Front Protection: |
IP55 |
| Power supply: |
Rated voltage 100 to 240V AC, (±10%), 50/60Hz |
| Power consumption: |
Max 20 VA |
| General Approvals |
UL, CE, CSA |
| Power Supply Consumption: |
90 to 264 V AC, max. 20VA |
| Operating Temperature: |
0 to 50°C ( 40°C or less in close mounting side-by-side) |
| Relative Humidity: |
20 to 90% (non condensing) |
| Storage Temperature: |
-25 to 70°C |
| Dimensions: |
96W×96H×100D (From the front panel surface) (mm) |
| Mounting: |
Direct panel mounting; mounting bracket, one each for upper and lower mounting |
| Weight: |
0.5 kg |