Yokogawa PR300 Specifications |
Phase and Wire
System |
- Universal three-phase three-wire system (switch the setting from single-phase two-wire system, single-phase three-wire system, or three-phase three-wire system)
- Universal three-phase four-wire system (switch the setting from single-phase two-wire system, single-phase three-wire system, three-phase three-wire system, or three-phase four-wire system)
- Three-phase four-wire system (2.5 element)
|
Frequency |
45 to 65 Hz |
Rated Input Voltage |
Rated Voltage |
Voltage Range (Variable) |
The primary voltage of VT |
Allowable Input Voltage |
120 V |
150 V |
900 kV |
150 V |
240 V |
300 V |
1800 kV |
300 V |
480 V |
600 V |
3600 kV |
600 V |
|
Rated Input Current |
Rated Current |
Current Range (Fixed) |
The primary current of CT |
Allowable Input Current |
1 A |
1 A |
32 kA |
1.2 times the current range (continuous)
Twice the current range (10 seconds) or
10 times the current range (3 seconds) |
5 A |
5 A |
160 kA |
|
Rated Input Power
and Measuring Range
(When VT and CT are
used, their respective
secondary values) |
Single-phase two-wire system |
Input (AC) |
Rated
Power |
Input
Measuring
Range |
Approximate
Consumed VA |
Voltage |
Current |
120 V / 1 A |
100 W |
- 120 to 120 W |
0.2 VA |
0.2 VA |
120 V / 5 A |
500 W |
-600 to 600 W |
240 V / 1 A |
200 W |
-240 to 240 W |
0.4 VA |
240 V / 5 A |
1000 W |
-1200 to 1200 W |
480 V / 1 A |
400 W |
-480 to 480 W |
0.8 VA |
480 V / 5 A |
2000 W |
-2400 to 2400 W |
|
Single-phase three-wire system |
Input (AC) |
Rated
Power |
Input
Measuring
Range |
Approximate
Consumed VA |
Voltage |
Current |
240 V / 1 A |
200 W |
-240 to 240 W |
0.2 VA/
phase |
0.2 VA/
phase |
240 V / 5 A |
1000 W |
-1200 to 1200 W |
|
Three-phase three-wire system |
Input (AC) |
Rated
Power |
Input
Measuring
Range |
Approximate
Consumed VA |
Voltage |
Current |
120 V / 1 A |
200 W |
-240 to 240 W |
0.2 VA/
phase |
0.2 VA/
phase |
120 V / 5 A |
1000 W |
-1200 to 1200 W |
240 V / 1 A |
400 W |
-480 to 480 W |
0.4 VA/
phase |
240 V / 5 A |
2000 W |
-2400 to 2400 W |
480 V / 1 A |
800 W |
-960 to 960 W |
0.8 VA/
phase |
480 V / 5 A |
4000 W |
-4800 to 4800 W |
Input measuring range when VT and CT are used |
|
Three-phase four-wire system |
Input (AC) |
Rated
Powe |
Input
Measuring
Range |
Approximate
Consumed VA |
Voltage |
Current |
*120 V / 1 A |
300 W |
-360 to 360 W |
0.2 VA/
phase |
0.2 VA/
phase |
120 V / 5 A |
1500 W |
-1800 to 1800 W |
*240 V / 1 A |
600 W |
-720 to 720 W |
0.4 VA/
phase |
240 V / 5 A |
3000 W |
-3600 to 3600 W |
*480 V / 1 A |
1200 W |
-1440 to 1440 W |
0.8 VA/
phase |
480 V / 5 A |
6000 W |
-7200 to 7200 W |
*Input specification of 1 A AC is not available for 2.5 element. |
|
The primary input power (Secondary rated power x 1.2 x VT ratio x CT ratio) is smaller than 10 GW and the
value calculated by the following equation is within the input measuring range mentioned above.
|
Digital Input Specifications |
For digital input, either the optional integration start/stop or the demand alarm release can be used. If demand measurement is specified for an optional measuring function, digital input enters demand alarm release status. In this case, the optional integration start/stop cannot be used. |
Function |
Starts or stops optional integration. |
Number of Inputs |
1 |
Input Signal |
Voltage signal*
ON signal: 4.5 to 25 V DC
OFF signal: within ± 1 V DC |
Minimum ON time |
50 ms |
* A special order can be placed for no-voltage contact.
Note: Optional integration control is also possible via communication. Once control is performed by digital input, only digital input-based control is available. Communication-based control is no longer possible until the power is turned off/on or remote reset is executed. |
Demand alarm release (when demand measurement is specified) |
Function |
Cancels demand alarm. |
Number of Inputs |
1 |
Input Signal |
Voltage signal*
ON signal: 4.5 to 25 V DC
OFF signal: within ± 1 V DC |
Minimum ON time |
50 ms |
* A special order can be placed for no-voltage contact. |
Analog Output Specifications (When Analog Output is Specified) |
Function |
Converts measurement data into DC current for output. |
Measurement Item for Output |
One item selected from active power, reactive power, apparent power, voltage (1 to 3), current (1 to 3),
power factor, and frequency |
Output Signal |
4 to 20 mA DC |
Output Accuracy |
Measurement accuracy of measurement item for output + ( ± 0.5% of F.S.) |
Allowable Load Resistance |
0 to 600Ω |
Response speed |
2 seconds or less (until ± 1% of the final value is reached) |
Setting Item |
Measurement item for output and the lower and upper limits of scaling.
Initial value: active power (W), lower limit of scaling: 50% (0 W), upper limit of scaling: 100% (maximum value of
the input measuring range W)
Scaling setting condition: upper limit of scaling - lower limit of scaling ≥ 50% |
Setting Range of
Lower/Upper Limits
of Scaling According to
Measurement Item
for Output |
Active power |
rated power (W) to rated power (W) |
Reactive power |
rated power (var) to rated power (var) |
Apparent power |
0 to rated power (VA) |
Voltage (1 to 3) |
0 to voltage range (V) |
Current (1 to 3) |
0 to current range (A) |
Power factor |
(LEAD)0.5 to 1 to (LAG)0.5 |
Frequency |
45 to 65 (Hz) |
Pulse Output Specifications (When Pulse Output is Specified) |
Function |
Outputs pulses proportional to energy. |
Measurement Item for Output |
One item selected from active energy, regenerative energy, reactive energy (LEAD, LAG), and apparent energy |
Number of Outputs |
1 |
Output Signal |
Open collector |
Contact Capacity |
30 V DC at 200 mA |
Pulse Unit |
0.1 to 5000.0 kWh/pulse* (set in 100 Wh increments) |
Setting Item |
Measurement item for output, pulse unit, and ON pulse width
Initial value: active energy (kWh)
pulse unit: 1 kWh/pulse
ON pulse width: 50 ms |
* The units are kvarh/pulse for reactive energy and kVAh/pulse for apparent energy. |
Demand Alarm Output Specifications (When Demand Measurement is Specified) |
Function |
Outputs an alarm if the measured demand value exceeds the set demand alarm point. |
Output Signal |
Open collector |
Contact Capacity |
30 V DC at 200 mA |
Alarm Release Function |
Automatic release: Cancels the alarm if demand falls below the demand alarm point when the next measurement is performed.
Manual release*: Holds the status of an alarm that occurred once. Cancels the alarm by digital input or the operation key, or via communication. |
* Refer to “Demand alarm release” of the Digital Input Specifications. |
Standard Performance |
Accuracy Rating |
Active energy/optional active energy (Wh) |
±0.5% (EN60687 accuracy: class 0.5 or equivalent) |
Active power (W) |
±0.5% of F.S. |
Voltage (V) |
±0.25% of F.S. (voltage rms) |
Current (A) |
±0.25% of F.S. (current rms) |
Frequency (Hz) |
±0.5 Hz |
Demand |
±0.5% |
Calculation Accuracy |
The value is calculated to an accuracy of ±1 digit from the measured value for reactive energy, apparent energy,
reactive power, apparent power, power factor or current*.
* Current is only for the 2.5 element measurement. |
Backup upon Power Failure |
The last integrated values obtained immediately before the power failure are held for active energy,
regenerative energy, reactive energy, and apparent energy. |
Insulation Resistance |
Between each of the voltage input, current input, power,
ground, digital input, pulse output, analog output, RS485
communication output, Ethernet communication output, and
alarm output terminals |
100 MΩ or more (at 500 V DC) |
Withstand Voltage |
Between each of the voltage input, current input, power, and
ground terminals: |
2500 V AC for 1 minute |
Between (the voltage input, current input, power and ground
terminals) and the digital input, pulse output, analog output,
alarm output, RS-485 communication output, and Ethernet
communication output terminals: |
2500 V AC for 1 minute |
Between each of the digital input, pulse output, analog output,
alarm output, and (RS-485 communication output, Ethernet
communication output) terminals: |
1000 V AC for 1 minute |
Between the RS-485 communication output, and Ethernet
communication output terminals: |
500 V AC for 1 minute |
Impulse Withstand Voltage |
Between all of the voltage input, current input, and power terminals and the ground terminal:
Between all of the output and ground terminals and all of the voltage input and current input terminals:
6 kV (1.2/50 μ s), 10 times for positive and negative |
Effects of Changes in Ambient
Temperature |
± 0.03%/ ° C for a temperature change rate of 10 ° C/h or less (when 0.05 In ≤ I ≤ I max, power factor = 1)
±0.05%/ ° C for a temperature change rate of 10 ° C/h or less (when 0.1 In ≤ I ≤ I max, power factor = LAG 0.5)
In: rated current, I: present current input |
Effects of Power Supply Voltage
Variations |
Active power: ±0.25%
Voltage/Current: ±0.125%
(for variations within the power supply operating range (when 0.01 In and power factor = 1)) In: rated current |
Effects of Input Frequency |
Active power: ±0.25%
Voltage/Current: ±0.125% (for variation of 45 to 65 Hz) |
Power Supply |
100-240 V AC ±10% (50/60 Hz) or 130-300 V DC ±15% |
Power Consumption |
AC drive: 10 VA maximum
DC drive: 5 W maximum |