Measurement Performance |
Measurement range |
0 … 100 %RH, non-condensing |
Accuracy at temperature range +10 … +40 °C (+50 … +104 °F) |
0 … 90 %RH |
±1.7 %RH |
90 … 100 %RH |
±2.5 %RH |
Accuracy at temperature range -5 … +10 °C, +40 … + 55 °C (+23 … +50 °F, +104 … +131 °F) |
0 … 90 %RH |
±3 %RH |
90 … 100 %RH |
±4 %RH |
Stability in typical HVAC applications |
±0.5 %RH/year |
Humidity sensor |
Vaisala HUMICAP 180R |
Measurement range |
-5 … +55 °C (+23 … +131 ºF) |
Accuracy at +20 … +30 °C (+68 … +86 °F) |
±0.2 °C (± 0.36 °F) |
Accuracy at +10 … +20 °C, +30 … +40 °C (+50 … +68 °F, +86 … +104 °F) |
±0.3 °C (± 0.54 °F) |
Accuracy at -5 … +10 °C, +40 … +55 °C (+23 … +50 °F, +104 … +131 °F) |
±0.5 °C (± 0.90 °F) |
Temperature sensor |
Digital temperature sensor |
Operating Environment |
Operating temperature |
-5 … +55 °C (+23 … +131 °F) |
Storage temperature |
-30 … +60 °C (-22 … +140 °F) |
EMC compliance |
EN61326-1, Industrial Environment |
Mechanical Specifications |
IP rating |
IP30 |
Weight |
155 g (5.5 oz) |
Standard housing color |
White (RAL9003(1)) |
Optional housing color (configurable models only) |
Black (RAL9005(1)) |
Housing material |
ABS/PC, UL-V0 approved |
Output connector |
Screw terminals
Max. wire size 2 mm2 (AWG14) |
Service port connector |
4-pin M8 |
(1) RAL code is only indicative with potential small variations in color shade. |
Inputs and Outputs |
Service port |
RS-485 line for temporary service use |
Current Output Models |
Outputs |
2 x 4 … 20 mA, loop powered |
Loop resistance |
0 … 600 Ω |
Supply voltage |
20 … 28 VDC at 500 Ω load
10 … 28 VDC at 0 Ω load |
Isolation between output channels |
500 VDC |
Voltage Output Models |
Outputs |
2 × 0 … 5 V or 2 × 0 … 10 V |
Load resistance |
10 kΩ min. |
Supply voltage |
18 … 35 VDC, 24 VAC ±20 % 50/60 Hz |
Max. current consumption |
12 mA
Max. with relay 25 mA |
Relay |
1 pc (max 50 VDC/50 VAC, 500 mA) |
Digital Models |
Supply voltage |
18 … 35 VDC, 24 VAC ± 20 % 50/60 Hz |
Max. current consumption (with 120 Ω termination) |
30 mA at 24 VDC |
Output type |
RS-485 (galvanic isolation, 1.5 kV) |
RS-485 end of line termination |
Enable with jumper, 120 Ω |
Supported protocols |
BACnet MS/TP or Modbus RTU
(selectable by DIP switch) |
BACnet MS/TP Operating mode |
Selectable Master/Slave |
Address range, master mode |
0 … 127 |
Address range, slave mode |
128 … 255 |
Modbus RTU address range |
0 … 247 |