| MAINS ANALYSER |
| Measurement Circuit |
Single Phase with standard mains connector |
| Current Rating |
16A rms continuous, or national connector rating if lower |
| Voltage Ranges |
115V (±200V pk) 230V (±400V pk) |
| Current Ranges |
±24mA pk to ±400A pk in fifteen 2:1 ranges |
| Frequency Range |
43 - 67 Hz |
| Shunt Resistance |
3mΩ |
| Sampling Rate |
300 points per cycle |
| Basic Accuracy |
Better than 0.2% ±1mA, up to 16A |
| Measured Parameters |
Vrms, Vpk, Arms, Apk, Crest factors, THD, W, VA, Power factor, Frequency, Inrush current |
| Monitor Outputs |
Re-constructed Voltage and Current Signals |
| HARMONICS ANALYSER |
| Measurements |
1st harmonic to 40th harmonic |
| Current Rating |
16A rms continuous, or national connector rating if lower |
| Voltage Ranges |
115V (±200V pk) 230V (±400V pk) |
| Current Ranges |
±24mA pk to ±400A pk in fifteen 2:1 ranges |
| Frequency Range |
43 - 67 Hz |
| Shunt Resistance |
3mΩ |
| Transforms Window |
Continuous 4, 10, 12 or 16 cycle Discrete Fourier Transforms |
| Basic Accuracy |
Better than 5% of limit or 0.2% of selected range (whichever is the greater) ± 1mA |
| VOLTAGE FLUCTUATIONS & FLICKER METER |
| Measurements |
Voltage fluctuations dmax, dc, d(t) and flicker Pst and Plt to EN61000-3-3 and EN61000-4-5 |
| Current Rating |
16A rms continuous, or national connector rating if lower |
| Voltage Ranges |
115V (±200V pk) 230V (±400V pk) |
| Fluctuation Range |
25% max. (relative to nominal voltage) |
| Flickermeter Range |
Voltage change up to 20% (sinewave change) or 10% (low repetition rate rectangular change) relative to AGC level. Equivalent to 6400 pu on 8.8 Hz sinewave |
| Flickermeter AGC |
Up to ± 5% |
| Flickermeter Accuracy |
Better than 5% for Pst range 0·7 to 10·0 |
| Frequency Range |
50 or 60 Hz (operates over 43 – 67 Hz) |
| Report Printing |
Tabular listing of voltage variations, Pst classifier and Pst in each Plt interval |
| GENERAL |
| Display |
320 x 240 pixel backlit LCD |
| Clock |
Realtime clock for time/date stamping of Report data |
| Interfaces |
Parallel Printer, RS-232, USB |
| Instrument Supply |
230V or 115V ±14%, 48 to 65Hz |
| Operating Range |
+5°C to 40°C, 20-80% RH |
| Storage Range |
–10°C to +60°C |
| Dimensions |
357 x 132 x 235mm (WxHxD) |
| Weight |
4.4 kg |
| Safety |
Complies with EN61010-1 |
| EMC Compliance |
Complies with EN61326-1 |