Model |
Z10 |
Z20 |
Z36 |
Z60 |
Z100 |
Load Regulation |
CV |
2mV + 0.01% of rated voltage over 0 - 100% load change |
Line Regulation |
CV |
2mV + 0.01% of rated voltage over a 85 - 132 or 170 - 265VAC line change |
Recovery Time (1) |
CV |
1ms |
Temperature Coefficient |
CV |
30ppm/°C following 30 minute warm up |
Temperature Stability |
CV |
0.02% of rated voltage over 8 hours following 30 minute warm up time |
Warm up Drift (2) |
CV |
<0.05% of rated voltage + 2mV of rated output voltage |
Up programming response time (10-90% or 90-10% of Vmax) |
CV |
15ms |
30ms |
30ms |
50ms |
50ms |
Down programming resp time (CV) (10-90% or 90-10% of Vmax) |
Full load |
10ms |
30ms |
30ms |
50ms |
50ms |
Down programming resp time (CV) (90-10% of Vmax) |
Zero load |
190ms |
200ms |
250ms |
310ms |
900ms |
Load Regulation |
CC |
5mA + 0.01% of rated current over 0 - 100% Vout change |
Load Regulation thermal drift |
CC |
< 0.05% of rated current over 30 minutes after load change |
Line Regulation |
CC |
2mA + 0.01% of rated current over a 85 - 132 or 170 - 265VAC line change |
Temperature Coefficient |
CC |
100ppm/C of rated current after 30 minute warm up time |
Temperature Stability |
CC |
0.05% of rated current over 8 hours following 30 minute warm up time |
Warm up Drift (2) |
CC |
<±0.1% of rated current |
Vout & Iout programming & readback resolution |
Digitally |
< 0.012% of rated voltage/current |
Vout & Iout programming & readback accuracy |
Digitally |
< 0.05% of rated voltage, < 0.1% of rated current |
Voltage & Current Programming |
Analog |
By either Voltage (0-5V or 0-10V) or Resistance (0-5k or 0-10k) |
Voltage & Current Monitoring |
Analog |
0-5V or 0-10V Voltage (user selectable), ±1% accuracy |
Overvoltage Shutdown (user programmable) |
V |
0.5 - 12 |
1 - 24 |
2 - 40 |
5 - 66 |
5 - 110 |
Overtemperature Protection |
- |
User selectable - latched or non-latching |
Display - Voltage |
- |
4 digits. Accuracy 0.5% of rated voltage or current ±1 count |
Remote On/Off |
- |
By applied voltage or dry contact relay (user selectable logic) |
Output Good |
- |
Open Collector, Low on fail |
Model |
Z10 |
Z20 |
Z36 |
Z60 |
Z100 |
Remote Sense Compensation (per wire) |
V |
1 |
1 |
2 |
3 |
5 |
Communication Interface |
- |
RS232, RS485 & USB standard, IEEE488 (GPIB) & LAN optional |
Series Operation |
- |
Up to two identical units (with external diodes) |
Parallel Operation |
- |
Up to six units in master-slave configuration |
Input Voltage / Frequency (3) |
- |
85-265VAC, 47-63Hz |
Inrush Current |
- |
< 25A |
Hold Up Time (Typical) |
ms |
16ms |
Power Factor Correction |
- |
Complies with EN61000-3-2 Class A (0.99 typ) |
Operating Temperature |
°C |
0 - 50°C |
Storage Temperature |
°C |
-20 to +85°C |
Humidity (non condensing) |
%RH |
Operating: 10 - 90%RH, Storage 10 - 95%RH |
Cooling |
- |
Internal temperature controlled fan |
Withstand Voltage |
- |
I/P to GND 2kVAC, I/P to O/P 3kVAC, O/P to GND 1380VDC 1 min |
Insulation Resistance |
- |
>100M at 25°C & 70%RH |
Vibration (non operating) |
- |
IEC60068-2-64 |
Shock |
- |
<20G, half sine, 11ms. IEC60068-2-27 |
Safety Agency Certifications |
- |
UL61010-1, EN61010-1, IEC61010 (Designed to meet UL/EN60950-1) |
Immunity |
- |
IEC61326 (Designed to meet EN55022 / EN55024) |
Conducted & Radiated EMI |
- |
EN55022-B, FCC part 15-B, VCCI-B |
Size (H x W x D) (Excluding handles and busbars) |
mm |
Standard body 83 x 70 x 350mm; Wide Body 83 x 105 x 350mm |
Weight |
kg |
Standard body 1.9kg, Wide body 2.4kg |
Warranty |
yrs |
Five Years |
Notes:
(1) Recovery to within 0.5% of rated voltage after a load change of 10-90% (Output current 10-100% of Imax)
(2) During 30 minute warm up time after power on
(3) Derate for 85-100 VAC; Z10-72-U (66A), Z20-40-U (36A), Z36-24-U (20A), Z60-14-U (12.5A), Z100-8-U (7.5A) |