Model: SXAX20E Specifications |
Load Rating |
15/20 Amps at 120 Volts (SX-AX15E / SX-AX20E) |
Power Requirement (no load) |
5 Watts |
Surge Let- Through Voltage (6000-volt surge) |
0 Volts |
UL 1449 Adjunct Classification Test Results |
1000 Surges, 6000 Volts, 3000 Amps, B3 pulse; measured suppressed voltage, 170 Volts; no failures |
Maximum Applied Surge Voltage |
6000 volts* |
Maximum Applied Surge Current |
Unlimited, due to current limiting* |
Maximum Applied Surge Energy |
Unlimited, due to current limiting* |
Endurance (C62.41-1991 Category B3 pulses) |
1 KV > 500,000; 3 KV > 10,000; 6 KV > 1000 |
EMI/RFI Filter, Normal Mode (50-ohm load) |
40 dB@100 KHz, 50 dB@300 KHz; 50 dB@3 MHz, 50 dB@30 MHz |
EMI/RFI Filter, Common Mode (50-ohm load) |
18 dB@300 KHz, 30 dB@1 MHz; 50 dB@5 MHz, 50 dB@20 MHz |
Under-Voltage Auto Shutdown |
Adjustable from 80V to 110V, or disabled |
Over-Voltage Auto Shutdown |
Adjustable from 130V to 160V |
Over-Current Auto Shutdown |
Adjustable from 1A to 20A, or disabled |
Over-Temperature Auto Shutdown |
Adjustable from 70 to 100°F, or disabled |
Voltage |
± 1% from 90 – 160 VRMS |
Current |
± 1% from 0.1 – 20 ARMS (Resistive) |
Measurement Accuracy |
Power |
± 5% from 0.1 – 2400 WRMS (Resistive) |
Energy |
± 5% kWh |
Temperature |
± 5.3°C from -25 – 105°C |
Network Port |
10/100 Ethernet connection on Female RJ-45, Auto Negotiating with 10/100/1000 network connections with Link and Activity LEDs |
Serial Port |
RS-232 on Female 9-pin D-subminiature, DCE |
Temperature Sensor Input |
2 x screw terminal |
Auxiliary Relay Outputs |
(2) 3 x screw terminal |
Contact Closure Input |
2 x screw terminal |
Dimensions |
19” W x 12.25” D x 1.75” H (Single Rack Space) |
Weight |
13 lb |
Temperature Range |
5°C to 35°C |
Humidity Range |
0% to 95% R.H. Non-condensing |
Agency Listings |
ETL Certified to UL 1449 |