| Model: SA82AR Specifications |
| Load Rating |
8 amps @ 120 volts |
| Power Requirement (no load) |
10 watts |
| UL 1449-2 Adjunct Classification Test Results |
1000 surges, 6000 volts, 3000 amps, C1 pulse, measured suppressed voltage 290 volts, no failures |
| Federal Guidelines |
Grade A, Class 1, Mode 1 (CID A-A-55818) A |
| EMI/RFI Filter, Normal Mode (50-ohm load) |
40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz |
| EMI/RFI Filter, Common Mode (50-ohm load) |
18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz |
| Maximum Applied Surge Pulse Joule Rating |
Unlimited, due to current limiting (8 x 20 µs)* |
| Maximum Applied Surge Pulse Voltage |
6000 Volts* |
| Maximum Applied Surge Pulse Current |
Unlimited, due to current limiting* |
| Endurance |
IEEE C62.41-1991 Category B3 (C1) |
| Pulses |
m1 kV>500,000; 3 kV>10,000; 6 kV>1000 |
| Overvoltage Shutdown |
145 Volts (resume at 135 volts) |
| Dimensions |
11.375" W x 7.625" D x 1.8125" H |
| Weight |
4.75 lbs |
| Temperature Range |
5º to 35º C |
| Humidity Range |
5% to 95% R.H., non-condensing |
| Agency Listings |
TUV Certified to UL 60950 Listed I.T.E.
File No. E225914
ETL Certified to UL 1449
ETL Certified to UL 1283 |
| CE |
Directives 89/336/EEC, 92/31/EEC and 93/68/EEC
EN 60950
EN55022: 1998 Class B |
| FCC |
Part 15 Class B |
| NETWORK |
Single 10/100 Unshielded Twisted Pair Ethernet Jack
IP Addressed: DHCP Assigned or Static
Internal HTTP Web Server
Forms Processing Browser Required
Internal Telnet Server |