Size |
PS4550 Analyzer: 3.88" (9.86 cm) W x 7.72" (19.61 cm) L x 1.58" (4.01 cm) Deep at bottom end; 2.14" (5.44 cm) Deep at top end |
Weight |
PS4550 Analyzer: 1.1 lbs (0.5 kg) |
Operating Range |
32 - 122 degrees F (0 - 50 degrees C) Relative humidity to 70% (non-condensing) |
Power Requirement |
12V DC @ 500 mA |
Battery Life |
8-10 hours after 4 hour charge |
Battery Type |
Li-ion |
Sampling Rate |
8 microseconds for Voltage and Current, continuous/simultaneous |
Safety |
600V CAT IV, 1000V CAT III |
SD Card Slot |
Accepts SD Cards to 32GB (SDHC) |
Logging Period (Resolution) |
1 Second - 99 Minutes (set by user) |
Logging Duration (Length of session) |
up to 2 years, depending on memory allocation |
Internal Data Retention |
8 years |
Other Features |
Crest Factor, K Factor, Peak Demand Period, Peak Demand of Peak, Demand Period, Duty Cycle, On/Off Cycle %, Avg. On Time, Avg Off Time |
Direct Measurement Range |
1 - 1,000V (up to 15,000V with optional 15KVP) |
Measurement Range |
1 - 6 megavolts (using input ratios with PTs) |
Accuracy |
0.1% of reading ±0.3 Vrms |
Direct Measurement Range |
1 - 6,000A AC (down to 0.002A with optional HA-GFD, DC to 2,000A with optional DC2000, etc) |
Display Range |
0.001 - 6 megamps (using input ratios and CTs) |
Accuracy |
±1 % of reading +/-0.2A in low range, +/- 2.0A in high range |
Direct Measurement Range |
1 - 18 megawatts (assuming 1000V, 6000A, PF=1.00, 3-phase power) |
Display Range |
from 0.002W (using HA-GFD) to 999 megamps (using input ratios and CTs) |
Accuracy |
±0.5 % of reading +/- the accuracy of the current probes |