Model: P-3 Specifications |
Description |
Voltage and Continuity Tester |
AC/DC voltage measurement and indication |
- on LED bargraf for values: 12, 24, 50, 120, 230, 400, 690 V (indication of voltage with and without batteries),
- display of measurement result in the LCD screen,
- determination of voltage: alternating or polarisation of constant voltage. |
Resistance measurement and circuit continuity test |
- display of measurement result in the LCD screen,
- signaling for resistance <400 kΩ. |
Indicator of phase rotation |
indication of phase sequence for voltage >100 V |
Single pole test for phase detection |
- indication by means of touch electrode,
- optical and acoustic signaling for voltage >50 V. |
RCD test |
RCD test IΔn ≤100 mA. |
Identification and adjustment of phase |
- phase determination at given socket referring to the other one,
- possibility of phase determination at given socket with using additional transmitter - without time limit related to the synchronization of runs. |
Terminals |
Ø 0.08" / 2 mm and 0.16" / 4 mm |
Illumination of measurement point |
Yes |
DATA HOLD function |
Yes - for holding measured values |
Meter meets the requirements of the standards EN 61010 |
IEC/EN 61243 - 3 EMC |
AC/DC voltage measurement |
Range |
Resolution |
Accuracy (AC) |
Accuracy (DC) |
6.0 to 49.9 V
50 to 750 V |
0.1 V
1 V |
±(3% m.v. +4 digits)
±(2% m.v. +3 digits) |
±(3% m.v. + 3 digits) |
Resistance measurement |
Range |
0 to 1,999 Ω |
Resolution |
1 Ω |
Accuracy |
±(3% m.v. + 8 digits) |