| OUTPUT |
| Output Volt Amp Capacity (VA) |
750 |
| Output Watt Capacity (watts) |
600 |
| Output kW capacity |
1.2 |
| Output power factor |
0.8 |
| Crest Factor |
3.1 |
| Nominal Output Voltage(s) Supported |
100v; 110v; 120v |
| Nominal Voltage details |
120V default |
| Frequency compatibility |
50 / 60 Hz |
| Frequency compatibility details |
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start |
| Output voltage regulation (line mode) |
+/- 2% |
| Output voltage regulation (Economy line mode) |
+/- 10% |
| Output voltage regulation (Battery mode) |
+/- 2% |
| Built-in UPS output receptacles |
6 5-15R outlet(s) |
| Built-in controllable switched load banks |
Two switchable 5-15R load banks (bank 1 - two outlets, bank 2 - four outlets) |
| Basic PDU options |
PDU1215 (1U / 13 5-15R outlets); PDUNV (1U / 2 C19, 12 C13 outlets); PDU1415 (0U / 14 5-15R outlets); PDUV15 (0U / 12 5-15R outlets) |
| Metered PDU options |
PDUMH15 (1U / 13 5-15R outlets); PDUMH15AT (1U / 8 5-15R outlets)*; PDUMV15 (0U / 16 5-15R outlets) |
| Switched PDU options |
PDUMH15ATNET (1U / 8 5-15R outlets)*; PDUMV15NET (0U / 16 5-15R outlets) |
| External PDU redundancy options |
*ATS switch options PDUMH15AT & PDUMH15ATNET support dual UPS and hot-swappable UPS configurations |
| Output AC waveform (AC mode) |
Sine wave |
| Output AC waveform (battery mode) |
Sine wave |
| INPUT |
| Rated input current (at maximum load) |
12A |
| Nominal Input Voltage(s) Supported |
100V AC; 110V AC; 120V AC |
| UPS input connection type |
5-15P |
| Input circuit breaker |
20A |
| UPS Input cord length (ft.) |
10 |
| UPS Input cord length (m) |
3 |
| Recommended Electrical Service |
15A 120V |
| BATTERY |
| Full load runtime (minutes) |
5 min. (1200w) |
| Half load runtime (minutes) |
14 min. (600w) |
| Expandable battery runtime |
Extended runtime supported via optional external battery packs |
| External battery pack compatibility |
BP48V24-2U (limit 1); BP48V60RT3U (multi-pack compatible) |
| DC system voltage |
48V DC |
| Battery recharge rate (included batteries) |
Less than 6 hours from 10% to 80% |
| Replacement battery cartridge (internal UPS battery replacement) |
RBC94-2U |
| Battery Access |
Front panel battery access door |
| Battery replacement description |
Hot-swappable, user replaceable batteries |
| VOLTAGE REGULATION |
| Voltage regulation description |
Online, double-conversion power conditioning |
| Overvoltage correction |
2% output voltage regulation during overvoltages to 138 |
| Undervoltage correction |
2% output voltage regulation during undervoltages to 80 |
| Severe undervoltage correction |
2% output voltage regulation during undervoltages to 65 (under 70% load only) |
| LEDS ALARMS & SWITCHES |
| LED Indicators |
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats |
| Alarms |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
| Alarm cancel operation |
Power-fail alarm can be silenced using alarm-cancel switch |
| Switches |
2 switches control off/on power status and alarm-cancel/self-test operation |
| SURGE / NOISE SUPPRESSION |
| UPS AC suppression joule rating |
510 |
| UPS AC suppression response time |
Instantaneous |
| UPS Dataline suppression |
1 line TEL / DSL or 10Base T Ethernet protection |
| EMI / RFI AC noise suppression |
Yes |
| PHYSICAL |
| Installation form factors supported with included accessories |
4 post 19 inch rackmount (mounting rail kit included) |
| Installation form factors supported with optional accessories |
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND) |
| Primary form factor |
Rackmount |
| UPS / Power Module dimensions in primary form factor (height x width x depth / inches) |
3.5 x 17.5 x 19 |
| UPS / Power Module dimensions in primary form factor (height x width x depth / cm) |
8.9 x 44.4 x 48.3 |
| Installed whole system total rack space height (rack spaces) |
2U |
| Secondary form factor |
Tower (requires 2-9USTAND) |
| Installed whole system dimensions in secondary form factor (height x width x depth / inches) |
17.5 x 3.5 x 19 |
| UPS dimensions in secondary form factor (height x width x depth / cm) |
44.4 x 8.9 x 48.3 |
| UPS / Power Module weight (lbs) |
44.1 |
| UPS / Power Module weight (kg) |
20 |
| UPS Shipping dimensions (height x width x depth / inches) |
9.8 x 20.2 x 24 |
| UPS Shipping dimensions (height x width x depth / cm) |
24.8 x 51.4 x 61 |
| Shipping weight (lbs) |
54 |
| Shipping weight (kg) |
24.5 |
| UPS housing material |
Steel |
| Cooling method |
Fan |
| ENVIRONMENTAL |
| Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
| Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
| Relative Humidity |
0 to 95%, non-condensing |
| AC mode BTU / hr. (full load) |
609.7 |
| AC economy mode BTU / hr. (full load) |
260.4 |
| Battery mode BTU / hr. (full load) |
664.2 |
| AC economy mode efficiency rating (100% load) |
94% |
| COMMUNICATIONS |
| Communications interface |
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface |
| Network monitoring port description |
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications |
| PowerAlert software |
Included |
| Communications cable |
USB and DB9 cabling included |
| WatchDog compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
| LINE / BATTERY TRANSFER |
| Transfer time |
No transfer time (0 ms.) in online, double-conversion mode |
| Low voltage transfer to battery power (setpoint) |
80V (100% load), 65V |
| High voltage transfer to battery power (setpoint) |
138 |
| SPECIAL FEATURES |
| Cold Start (startup in battery mode during a power failure) |
Cold-start operation supported |
| High availability UPS features |
Automatic inverter bypass; Hot swappable batteries |
| Green & high efficiency features |
High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation |
| CERTIFICATIONS |
| UPS Certifications |
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI); Meets FCC Part 68 / Industrie Canada (telecommunications); ROHS (Reduction of Hazardous Substances) |
| WARRANTY |
| Product Warranty Period (U.S., Canada & Puerto Rico) |
2-year product warranty |