General Specifications |
Dimensions |
Size |
54.6 x 34.7 x 24.7 cm |
54.6 x 34.7 x 24.7 cm |
Weight |
Instrument |
24.9 kg (single case) |
(55 lb) |
Cable / Accessory Bag |
16.2 kg |
(35.7 lb) |
Environment |
Operating Temperature |
-10 .. 50°C |
(14..122° F) |
Storage Temperature |
-20 .. 70°C |
(-4..158° F) |
Relative Humidity |
5 .. 95 % r.h. non-condensing |
Standards |
Safety |
IEC 61010-1 (2010) |
EN 61010-1:2001(ZEK 01.4-08) |
EMC |
EN 61000-3-2 (2006)
EN 61000-4-3 (2010)
EN 61000-4-6 (2007) |
EN 61000-3-3 (2008)
EN 61000-4-4 (2004)
EN 61000-4-11(2004) |
EN 61000-4-2 (2009)
EN 61000-4-5 (2006)
EN 55011 +A1(2009) |
Drop Test |
IEC 60068-2-31 Edition 4.0 (face, corner, free fall) |
Shock & Vibration |
IEC 60068-2-6
IEC 60068-2-64 Edition 2.0 |
IEC 60068-2-27 |
MIL-STD-810G |
Aging Cycle |
MIL-T-28800 |
Inputs |
Power |
90 .. 264 VAC 50/60 Hz, 800 W, active PFC (acc. IEC61000-3-2) |
Measurement |
≤ 180 mA RMS |
Output |
Voltage |
25 .. 12’000 V RMS (@ 45 .. 70 Hz) |
Frequency |
15 .. 400 Hz (Voltage ≤ 5 kV) |
Current |
180 mA RMS |
DUT Capacitance |
max. 47 nF @ 12 kV RMS @ 50 Hz, max. 39 nF @ 12 kV RMS @ 60 Hz |
Measurement |
Resolution |
Accuracy |
Dissipation / Power Factor
tan / cos |
0.0001
0.01 % |
± 0.5 % rdg ± 0.0001 @ 50..60Hz
± 0.5 % rdg ± 0.01 % @ 50..60Hz |
Capacitance |
0.01 pF |
± 0.3 % rdg ± 0.3 pF |
Test Voltage |
1 V |
± 0.3 % rdg ± 1V |
Test Current |
0.1 μA |
± 0.3 % rdg ± 1 μA |
Watts / Power |
0.1 mW, mVA, mVAR |
± 0.8 % rdg ± 1 mW, mVA, mVAR |
Quality Factor |
0.0001 |
± 0.5 % rdg ±0.0001 |
Internal Reference |
100 pF Reference Capacitance, tan < 0.00001
Temperature coefficient < 0.01 % / K, Capacitance ageing < 0.01 % / year |
Safety Features |
Open Ground Detection
Security handheld switch, foot switch (optional)
internal warning indicator, external warning lamp (optional)
audible warning signal |
Interfaces |
USB 2.0 for Memory Stick, Ethernet, Thermal Printer |
Display |
7" TFT , 800 x 480, Colour Touch Screen |
Data Formats |
XML, CSV |
Record Values |
DF (tan δ)
PF (cos φ)
Capacitance Cx
Test Current Ix
Real Power P
Ref Current In
Phase-angle φ(Zx)
Conditions
Settings |
DF (tan δ)@20°C
PF (cos φ)@20°C
Resistance Rx
Mains frequency fm
Reactive Power Q
Capacitance Cn
Voltage URMS
Comments |
DF%(tan δ)
PF%(cos φ)
Inductance Lx
Noise frequency fn
S/N Ratio
Current Imag (Lp)
Insulation Temp.
Connection mode |
DF%(tanδ)@20°C
PF%(cos φ)@20°C
Frequency f
Apparent Power S
Quality Factor QF
Current Ife (Rp)
Temp.Corr.Factor K
Time/Date |
Calibration Interval |
2 years recommended |