| DC VOLTAGE |
| Range |
0.1 ÷ 999.9V |
| Resolution |
0.1V |
| Accuracy |
±(1.0%rdg + 3dgt) |
| Input impedance |
1MΩ |
| Overload protection |
1000VDC/ACrms |
| AC (AC+DC) TRMS VOLTAGE |
| Accuracy |
±(1.0%rdg + 3dgt) |
| Input impedance |
1MΩ |
| Overload protection |
1000VDC/ACrms |
| Max crest factor |
1.41 |
| Fundamental |
50/60Hz ± 15% |
| Frequency bandwidth |
42.5Hz ÷ 1725Hz |
| AC/DC VOLTAGE – MAX/MIN/CREST |
| Range |
0.5 ÷ 999.9V |
| Resolution |
0.1V |
| Accuracy |
±(3.5%rdg + 5dgt) |
| Response time |
1s |
| Overload protection |
1000VDC/ACrms |
| Input impedance |
1MΩ |
| Max crest factor |
1.41 |
| Fundamental |
50/60Hz ± 15% |
| Frequency bandwidth |
42.5Hz ÷ 1725Hz |
| DC CURRENT |
| Range |
0.1 ÷ 999.9A |
| Resolution |
0.1A |
| Accuracy |
±(2.0%rdg + 5dgt) |
| Overload protection |
1000ADC/ACrms |
| AC (AC+DC) TRMS CURRENT |
| Range |
0.1 ÷ 999.9A |
| Resolution |
0.1A |
| Accuracy |
±(2.0%rdg + 5dgt) |
| Overload protection |
1000ADC/ACrms |
| Max crest factor |
1.41 |
| Fundamental |
50/60Hz ± 15% |
| Frequency bandwidth |
42.5Hz ÷ 1725Hz |
| AC/DC CURRENT – MAX/MIN/CREST |
| Range |
0.5 ÷ 999.9A |
| Resolution |
0.1A |
| Accuracy |
±(3.5%rdg + 5dgt) |
| Response time |
1s |
| Overload protection |
1000VDC/ACrms |
| Max crest factor |
1.41 |
| Fundamental |
50/60Hz ± 15% |
| Frequency bandwidth |
42.5Hz ÷ 1725Hz |
| DYNAMIC INRUSH CURRENT DC, AC+DC TRMS |
| Range |
1.0 ÷ 99.9A |
| Resolution |
0.1A |
| PEAK Accuracy |
±(2.0%rdg + 5dgt) |
| Max RMS Accuracy |
±(2.0%rdg + 5dgt) |
| Overload protection |
1000ADC/ACrms |
| Crest factor |
3 |
| Sample frequency |
4kHz |
| Response time |
Peak: 1ms |
| Max RMS |
calculated on: 16.7, 20, 50, 100, 150, 200ms |
| Accuracy declared for frequency |
DC, 42. .. 69Hz |
| RESISTANCE AND CONTINUITY TEST |
| Range |
0.0Ω ÷ 199.9Ω, 200Ω ÷ 1999Ω, 2.00kΩ÷19.99kΩ, 20.0kΩ ÷ 29.9kΩ |
| Resolution |
0.1Ω, 1Ω, 0.01kΩ, 0.1kΩ |
| Accuracy |
±(1.0%rdg + 5dgt) |
| Buzzer |
1Ω ÷ 150Ω |
| Overload protection |
1000VDC/Acrms, 1000ADC/ACrms |
| FREQUENCY WITH TEST LEADS AND WITH JAWS |
| Range |
42.5 ÷ 69.0Hz |
| Resolution |
0.1Hz |
| Accuracy |
±(1.0%rdg + 5dgt) |
| Overload protection |
1000VDC/Acrms, 1000ADC/ACrms |
| Voltage range for frequency measurement |
0.5 ÷ 1000V / Current range for frequency measurement with jaws : 0.5 ÷ 1000A |
| PHASE SEQUENCE AND PHASE CONFORMITY |
| Voltage range |
100 ÷ 1000V |
| Frequency range |
42.5 ÷ 69Hz |
| Overload protection |
1000VDC/ACrms |
| Input impedance |
1MΩ |
| DC POWER |
| Range [kW] |
0.00 ÷ 99.99, 100.0 ÷ 999.9 |
| Resolution [kW] |
0.01, 0.1 |
| Accuracy |
±(3.0%rdg + 3dgt) |
| Input impedance |
1MΩ, Accuracy defined for voltage > 10V, current ≥ 2A |
| ACTIVE POWER, APPARENT POWER AC (AC+DC TRMS) |
| Range [kW, kVA] |
0.00 ÷ 99.99, 100.0 ÷ 999.9 |
| Resolution [kW, kVAR, kVA] |
0.01, 0.1 |
| Accuracy |
±(2.0%rdg + 3dgt) |
| Input impedance |
1MΩ, Accuracy defined for: sinusoidal waveform,42.5..69Hz, Voltage ≥ 10V, Current ≥ 2A, Pf ≥ 0.5 |
| REACTIVE POWER AC (AC+DC TRMS) |
| Range [kVAR] |
0.00 ÷ 99.99, 100.0 ÷ 999.9 |
| Resolution [kW, kVAR, kVA] |
0.01, 0.1 |
| Accuracy |
±(2.0%rdg + 3dgt) |
| Input impedance |
1MΩ, Accuracy defined for: sinusoidal waveform,42.5..69Hz, Voltage ≥ 10V, Current ≥ 2A, Pf ≥ 0.9 |
| ACTIVE ENERGY AC (AC+DC TRMS) |
| Range [kWh] |
0.00 ÷ 99.99, 100.0 ÷ 999.9 |
| Resolution [kWh] |
0.01, 0.1 |
| Accuracy |
±(2.0%rdg + 3dgt) |
| Input impedance |
1MΩ, Accuracy defined for: sinusoidal waveform,42.5..69Hz, Voltage ≥ 10V, Current ≥ 2A, Pf ≥ 0.5 |
| REACTIVE ENERGY AC (AC+DC TRMS) |
| Range [kVARh] |
0.00 ÷ 99.99, 100.0 ÷ 999.9 |
| Resolution [kVARh] |
0.01, 0.1 |
| Accuracy |
±(2.0%rdg + 3dgt) |
| Input impedance |
1MΩ, Accuracy defined for: sinusoidal waveform,42.5..69Hz, Voltage ≥ 10V, Current ≥ 2A, Pf ≥ 0.9 |
| Range |
0.20 ÷ 1.00 |
| Resolution |
0.01 |
| Accuracy |
±(2.0%rdg+2dgt) |
| Input impedance |
1MΩ, Accuracy defined for: sinusoidal waveform,42.5..69Hz, Voltage ≥ 10V, Current ≥ 2A |
| VOLTAGE AND CURRENT HARMONICS |
| Harmonic order |
0, 1 ÷ 25, THD% |
| Fundam. Freq. [Hz] |
42.5 ÷ 69.0 |
| Resolution [V], [A] |
0.1V /0.1A, 0.1% |
| Accuracy (values not zeroed) |
±(5.0%rdg+20dgt), ±(5.0%rdg+10dgt), ±(10.0%rdg+10dgt) |
| Mechanical characteristics |
| Dimensions (L x W x H) |
252 x 88 x 44mm |
| Weight (including battery) |
420g |
| Max conductor size |
45mm |
| Power supply |
| Battery type |
2 batteries 1.5V type AAA IEC LR03 |
| Battery life |
approx. 150 hours of continuous use in power/energy measures |
| Auto Power Off |
approx. 5 minutes of idleness |
| Display |
| Characteristics |
graphic dot matrix, 128x128pxl with backlight |
| Sample rate |
128 samples/period (@ 50Hz) |
| Display update rate |
1 times/sec |
| Conversion mode |
TRMS |
| Climatic conditions |
| Reference temperature |
23°C ± 5°C |
| Operating temperature |
0 ÷ 40 °C |
| Operating humidity |
<80%RH |
| Storage temperature |
-10 ÷ 60 °C |
| Storage humidity |
<70%RH |
| Reference guidelines |
| Comply with |
IEC/EN 61010-1, IEC/EN61010-2-032 |
| EMC |
IEC/EN61326-1 |
| Safety of test leads |
IEC/EN61010-031 |
| Insulation |
double insulation |
| Pollution degree |
2 |
| For inside use, max height |
2000m |
| Installation category |
CAT IV 600V to ground, max 1000V between inputs |
| Normative |
EMC 2004/108/CE Directive, LVD 2006/95/CE Directive, IEC/EN 61010-1, IEC/EN61187, CE MARK, EMC: IEC/EN61326 |