| DISPLAY AND MEMORY |
| Features |
TFT, touch screen, color graphic LCD, 320x240mm |
| Memory safety section |
999 locations, 3 marker levels |
| Memory PQA section |
8MB (not expanded) |
| Communication |
Optical-USB and built-in WiFi |
| POWER SUPPLY |
| Batteries |
6 x 1.2V(rechargeable) type AA or 6 x 1.5V type AA |
| Battery life |
> 500 test for each safety functions
> 6 hours in recording |
| Recharging time |
approx. 12 hours |
| External charger |
100-240VAC, 50/60Hz / 15VDC, CAT IV 300V |
| Auto Power OFF |
after 5 min of idleness (disabled) |
| MECHANICAL FEATURES |
| Dimensions (L x W x H) |
225 x 165 x 75mm |
| Weight (included batteries) |
1.2kg |
| WORKING ENVIRONMENTAL CONDITIONS |
| Reference temperature |
23°C 5°C |
| Working temperature |
0° 40°C |
| Allowed relative humidity |
<80%HR |
| Storage temperature |
-10 60°C |
| Storage humidity |
<80%HR |
| GENERAL REFERENCE STANDARDS |
| Safety of measuring instruments |
IEC/EN61010-1, IEC/EN61010-031, IEC/EN61010-2-032 |
| Product type standard |
IEC/EN61557-1-2-3-4-5-6-7-10 |
| EMC |
IEC/EN61326-1 |
| Technical documentation |
IEC/EN61187 |
| Insulation |
double insulation |
| Pollution degree |
2 |
| Encapsulation |
IP40 |
| Measurement category |
CAT IV 300V to ground, CAT III 350V to ground
max 600V among inputs |
| Max height of use |
2000m |
| TEST VERIFIES REFERENCE STANDARDS |
| Continuity test with 200mA |
IEC/EN61557-4 |
| Insulation resistance |
IEC/EN61557-2 |
| Earth resistance |
IEC/EN61557-5 |
| Fault loop impedance |
IEC/EN61557-3 |
| RCD test |
IEC/EN61557-6 (only Phase-Neutral-Ground systems) |
| Phase sequence |
IEC/EN61557-7 |
| Multifunction |
IEC/EN61557-10 |
| Prospective short circuit current |
EN60909-0 |
| Earth resistance on TN systems |
EN61936-1 + EN50522 |
| Power quality |
EN50160 |