Franklin Grid Celltron Advantage General Specifications |
Applications |
Tests individual Lead-Acid or Nickel-Cadmium cells or Monoblocs (up to 16Volts) in any common configuration, approximately 10-6000Ah. |
Voltage |
0.8 - 20.0 Volts DC |
Conductance |
100 - 19,990 Siemens |
Test Data Storage |
14000 tests stored internally, unlimited with USB drive connected |
Accuracy |
+/- 2% across test range, Voltage and Conductance |
Voltmeter Resolution |
5 mV |
User Programmable Functions |
• Preset values for over 250 battery types
• Low voltage alarm setting
• Low conductance warning
• Low conductance failure
• Test mode (push button/auto start) |
Calibration |
Franklin Electric will work with each customer to establish a regular calibration program if it is required by their quality or other management system |
Cable Options |
• Dual contact clamps
• Dual contact probes
• Custom cables by quotation |
Power Requirements |
• 7.2V, 2300AH, NiMH
• Internal swappable battery & charger |
Display |
LCD- FST 2.97 in x 2.81 in (75.4 mm x 71.3mm), 128 x 128 pixels, 40 degree viewing angle, contrast ratio 8, LED backlight |
Keypad |
Alph-numeric, Stainless-steel dome, polyester overlay, 1,000,000 actuations |
Data Transfer |
• USB Flash Drive (Type A)
• USB PC Interface (Type B)
• Infra-red, half-duplex IRDA protocol for printer |
Environmental Operating Range |
0 to +40C, 95% relative humidity, non-condensing |
Storage Temperature |
-20 to 50C |
Over Voltage Protection |
• Auto-reset disconnect
• Reverse polarity protected |
Housing Material |
Acid resistant ABS plastic santoprene overmold |
Analyzer Dimensions |
• 11 in x 4 in x 3 in
• 280 mm x 105 mm x 80 mm |
Case Dimensions |
• 19 in x 15.5 in x 7 in
• 485 mm x 395 mm x 180 mm |
Analyzer Weight |
1Kg / 2.6 lb |
Shipping Weight |
Approximately 5Kg/11 Lbs |