Power supply |
Voltage range: |
100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V using standard power cord (IEC 60320 C7) |
Power consumption: |
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) |
Efficiency: |
≥ 68.2 % (in accordance with energy efficiency regulations) |
Maximum no-load consumption: |
< 0.3 W only when powered using IEC 60320 input |
Mains power frequency: |
50/60 Hz ± 15 % |
Battery: |
Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
On-battery runtime: |
Four hours in standard operating mode, up to 5.5 hours in power saving mode |
Charging time: |
< 6 hours |
Data acquisition |
Resolution: |
16-bit synchronous sampling |
Sampling frequency: |
10.24 kHz at 50/60 Hz, synchronized to mains frequency |
Input signal frequency: |
50/60 Hz (42.5 to 69 Hz) |
Circuit types: |
1-ϕ, 1-ϕ IT, split phase, 3-ϕ delta, 3-ϕ wye, 3-ϕ wye IT, 3-ϕ wye balanced, 3-ϕ Aron/Blondel (2-element delta), 3-ϕ delta open leg, currents only (load studies) |
Data storage: |
Internal flash memory (not user replaceable) |
Memory size: |
Typical 10 logging sessions of 8 weeks with 1-minute intervals1 |
Basic interval |
Measured parameters: |
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
Averaging interval: |
User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
Averaging time min/max values: |
Voltage, Current: Full cycle RMS updated every half cycle Aux, Power: 200ms |
Demand Interval (Energy Meter Mode) |
Measured parameters: |
Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
Interval: |
User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off |
Standards compliance |
Power: |
IEEE 1459 |
Interfaces |
USB-A: |
File transfer via USB flash drive, firmware updates, max. supply current: 120 mA |
WiFi: |
File transfer and remote control via direct connection or WiFi infrastructure |
Bluetooth: |
Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1734, or 1732 upgrade option) |
USB-mini: |
Data download device to PC |
Voltage inputs |
Number of inputs: |
4 (3 phases and neutral) |
Maximum input voltage: |
1000 Vrms, CF 1.7 |
Input impedance: |
10 MΩ |
Bandwidth: |
42.5 Hz - 3.5 kHz |
Scaling: |
1:1 and variable |
Measurement category: |
1000 V CAT III/600 V CAT IV |
Current inputs |
Number of inputs: |
3, mode selected automatically for attached sensor |
Input voltage: |
Clamp input: 500 mVrms/50 mVrms; CF 2.8 |
Rogowski coil input: |
150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range |
Range: |
1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12”
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24”
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36”
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL |
Bandwidth: |
42.5 Hz - 3.5 kHz |
Scaling: |
1:1 and variable |
Auxiliary inputs |
Number of inputs: |
2 |
Input range: |
0 to ± 10 V dc, 1 reading/s |
Scale factor: |
Format: mx + b (gain and offset) user configurable |
Displayed units: |
User configurable (7 characters, for example, °C, psi, or m/s) |
Wireless connection |
Number of inputs: |
2 |
Supported modules: |
Fluke Connect ® 3000 series |
Acquisition: |
1 reading/s |
Operating temperature: |
-10 °C to +50 °C (14 °F to 122 °F) |
Storage temperature: |
-20 °C to +60 °C (−4 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F) |
Operating humidity: |
10 °C to 30 °C (50 °F to 86 °F) max. 95 % RH
30 °C to 40 °C (86 °F to 104 °F) max. 75 % RH
40 °C to 50 °C (104 °F to 122 °F) max. 45 % RH |
Operating altitude: |
2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
Storage altitude: |
12,000 m |
Enclosure: |
IP50 in accordance with EN60529 |
Vibration: |
MIL-T-28800E, Type 3, Class III, Style B |
Safety: |
IEC 61010-1
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031: CAT IV 600 V/CAT III 1000 V |
Electromagnetic compatibility (EMC): |
EN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 |
Temperature coefficient: |
0.1 x accuracy specification/°C |
Color LCD display: |
4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel |
Warranty: |
Instrument and power supply: two-years (battery not included)
Accessories: one-year
Calibration cycle: two-years |
Dimensions: |
Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in) |
Weight: |
Instrument: 1.1 kg (2.5 lb)
Power supply: 400 g (0.9 lb) |
Tamper protection: |
Kensington lock slot |