AC/DC Voltage Measurements |
Accuracy |
Range: 600.0 V
Resolution: 0.1 V
50 Hz to 400 Hz ± (% of Rdg + Digits): ±(2 % + 3) |
Input Impedance |
3 MΩ (nominal), < 100 pF |
Common mode rejection ratio (1 kΩ unbalanced) |
> 60 dB at dc, 50 or 60 Hz |
Overload Protection |
600 V rms or dc |
Earth bond resistance measurement |
Range/Resolution |
20.00 Ω 0.01 Ω
200.0 Ω 0.1 Ω
2000 Ω 1.0 Ω
20.00 kΩ 0.01 kΩ |
Accuracy |
±(1.5% + 3) |
Overload Protection |
2 V rms or dc |
Open Circuit Test Voltage |
> 4.0 V, < 8 V |
Short circuit current |
> 200.0 mA |
Insulation Specifications |
Measurement Range |
0.01 MΩ to 2000 MΩ |
Test voltages |
500 V, 1000V |
Test Voltage Accuracy |
+ 20 %, - 0 % |
Short circuit current |
1 mA nominal |
Auto Discharge |
Discharge time < 0.5 second for C = 1 µF or less |
Live circuit indicator |
Inhibit test if terminal voltage > 30 V prior to initialization of test |
Maximum Capacitive Load |
Operable with up to 1 µF load |
Measure Accuracy |
50 V: ±(3 % + 5)
100 V: ±(3 % + 5)
250 V: ±(1.5 % + 5)
500 V: ±(1.5 % + 5)
1000 V: ±(1.5 % + 5) to 2000 MΩ, ±(10 % + 3) above 2000 MΩ |
General Specifications |
Maximum voltage applied to any terminal: |
600 V ac rms or dc |
Storage temperature |
-40 °C to 60 °C (-40 °F to 140 °F) |
Operating temperature |
-20 °C to 55 °C (-4 °F to 131 °F) |
Temperature Coefficient |
0.05 x (specified accuracy) per °C for temperatures < 18 °C or > 28 °C (< 64 °F or > 82 °F) |
Relative Humidity |
0 % to 95 % @ 10 °C to 30 °C (50 °F to 86 °F)
0 % to 75 % @ 30 °C to 40 °C (86 °F to 104 °F)
0 % to 40 % @ 40 °C to 55 °C (104 °F to 131 °F) |
Vibration |
Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument |
Shock |
1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) |
Electromagnetic compatibility |
In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997) |
Safety |
Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV) |
Certifications |
CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition |
Batteries |
Four AA batteries (NEDA 15A or IEC LR6) |
Battery life |
Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off. |
Size |
5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L) |
Weight |
550 g (1.2 lb) |
IP Rating |
IP40 |
Altitude |
Operating: 2000 m CAT IV 600 V, 3000 m CAT III 600 V
Non-operating (storage): 12,000 m |
Over-range capability |
110% of range |
Included accessories |
TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe |