General Specifications |
|
Display |
Dual 7-segment 4-digit LED Displays: Red (PV), Green (SV) |
|
LED Status Indicators |
Control outputs (C1, C2), Alarm outputs (A1, A2), Autotune (AT), |
|
Manual mode (MA), and temperature units |
°C/°F |
|
Display range (span) |
-1999 to 9999 counts max (Programmable; limited by the range specified in Section 2.2 for each individual input type) |
|
Indicating Accuracy |
+0.2% Full Scale +1 digit |
|
Sampling Time |
4 readings per second |
|
Memory |
Nonvolatile. Meter memorizes user configuration on power-down |
|
Meter Enclosure |
ABS Plastic |
|
Front Panel |
Lexan (Drip and Dust Proof; IEC IP55, NEMA Equivalent) |
|
Power Supply |
85 to 260VAC 50/60 Hz (automatic switching) |
|
Power Consumption |
6 Watts |
|
Insulation Resistance |
>50M ohm |
|
Noise Rejection |
Common Mode - 110 dB typical, Normal Mode - 50 db typical |
|
Oper. Temp/Humidity |
14 to 122°F (-10 to 50°C), 90% RH max. |
|
Storage Temperature |
-4 to 140°F (-20 to 60°C) |
|
Dimensions (Cutout) |
3.58 x 3.58" ±0.02" (91.0 x 91.0mm ±0.5mm) |
|
Input Specifications |
|
Thermocouple inputs |
(Programmable) Types: J, K, T, E, B, R, S, N; Cold Junction Compensation |
|
Thermocouple Break Protection |
Upscale, Downscale |
|
Lead Wire Effect |
0.015%/ohm (Input impedance - 10 megohm) |
|
RTD input |
Pt 100 ohm (DIN, JIS); |
|
RTD Break Protection |
Upscale, Downscale |
|
Lead Wire Effect |
0.015%/ohm (automatically compensates if one lead wire is < 5 Ω) |
|
Current input |
4-20mA DC (27 Ω input resistance) |
|
Voltage input |
1-5V DC |
|
Thermocouple Ranges |
|
Type K |
-58 to 2498°F (-50 to 1370°C) |
|
Type J |
-58 to 1830°F (-50 to 1000°C) |
|
Type B |
32 to 3272°F (0 to 1800°C) |
|
Type T |
-454 to 752°F (-270 to 400°C) |
|
Type E |
-58 to 1382°F (-50 to 750°C) |
|
Type R |
32 to 3182°F (0 to 1750°C) |
|
Type S |
32 to 3182°F (0 to 1750°C) |
|
Type N |
-58 to 2372°F (-50 to 1300°C) |
|
RTD |
PT100 input ranges -392 to 932°F (-200 to 500°C), DIN or JIS |
|
Linear input range |
-1999 to 9999 display span (for 4-20mA, 1-5V, or special input) |
|
Temperature Stability |
5uV/°C typical |
|
Repeatability |
0.83 C (Thermocouple), 0.2°C (RTD), 1 digit (Linear) |
|
Output Specifications |
|
Control Output Relay |
1 & 2 5A at 110VAC, 3A at 220VAC, SPDT (Resistive Load) |
|
Note |
Relay 1 is called the Primary Output and Relay 2 the Secondary in this manual |
|
Optional Pulsed Outputs |
24V DC (DC drive for SSR) |
|
ON |
24V DC typical, 29V DC max. |
|
OFF |
0.3V DC max |
|
Optional Analog Control Output |
4-20mA DC |
|
Load limit |
600 Ω impedance max. |
|
Alarm/Timer Types |
High/Low Deviation and Absolute Alarms w/deadband adjust and Soak/Event ON/OFF Timers |
|
Alarm Output Relays |
1 and 2 5A at 110VAC, 3A at 220VAC, SPST (Resistive Load) |
|
Output Control Modes |
|
Proportional Band |
0.0 to 100.0% of Full Scale (Autotune) |
|
Integral Time |
0 to 3000 secs. (Autotune) |
|
Derivative Time |
0 to 3000 secs. (Autotune) |
|
Cycle Time |
1 to 100 secs. (0 sec for 4-20mA output) |
|
Anti-Reset |
Wind-Up Inhibits integral action outside of the Proportional Band |
|
Manual Reset |
0 to 100% of Prop. Band |
|
Hysteresis |
0.0 to 25.5% of Full Scale |