INPUT |
460XAC |
Phase |
1Ø or 3Ø |
Voltage |
1Ø : 200~240 VAC ± 10%
3Ø3W : 200~240 VAC ± 10%
3Ø4W : 346~416 VAC ± 10% |
Frequency |
47 - 63 Hz |
AC OUTPUT |
Power Rating |
1Ø2W |
6000 VA |
1Ø3W |
Total 4000 VA (2000 VA per phase) |
3Ø4W |
Total 6000 VA (2000 VA per phase) |
DC |
6000 VA |
Max. Current (RMS) |
1Ø2W |
5- 150 V |
55.2 A @ ≤110 V |
5 - 300 V |
27.6 A @ ≤220 V |
1Ø3W |
5 - 150 V |
18.4 A @ ≤110 V for per phase |
5 - 300 V |
9.2 A @ ≤220 V for per phase |
3Ø4W |
5 - 150 V |
18.4 A @ ≤110 V for per phase |
5 - 300 V |
9.2 A @ ≤220 V for per phase |
Inrush Current (peak) |
1Ø2W |
5- 150 V |
220.8 A |
5 - 300 V |
110.4 A |
1Ø3W |
5 - 150 V |
73.6 A for per phase |
5 - 300 V |
36.8 A for per phase |
3Ø4W |
5 - 150 V |
73.6 A for per phase |
5 - 300 V |
36.8 A for per phase |
Phase |
1Ø2W, 1Ø3W, 3Ø4W, provided option |
THD (Total Harmonic Distortion) |
<0.5% (Resistive Load) at 40.0~70.0 Hz and output voltage within the 80~140 VAC at Low Range or the 160~280 VAC at High Range.
<1% (Resistive Load) at 70.1~1000 Hz and output voltage within the 80~140 VAC at Low Range or the 160~280 VAC at High Range. |
Crest Factor |
≥3 |
Line Regulation |
± 0.1 V |
Load Regulation (Hardware) |
± (1% of output +1 V) at Resistive Load, <400 µS response time |
Load Regulation (Software) |
± 0.2 V, <1 S response time |
DC offset |
≤ ± 5 mV |
Poly-phase mode (3Ø4W) for per phase output setting |
Voltage |
Range |
5.0~300 VAC (phase), 8.6~520 VAC (line), 150/300 V Auto Range |
Accuracy |
± (0.2% of setting + 3 counts) |
Frequency |
Range |
40~1000 Hz Full Range Adjust |
Accuracy |
± 0.03% of setting |
Starting & Ending Phase Angle |
Range |
0~359º |
Accuracy |
±1º(45~65 HZ) |
Current Hi Limit |
5V~150 V |
0.01~18.40 A |
5V~300 V |
0.01~9.20 A |
Accuracy |
± (2.0% of setting + 2 counts) |
OC Fold Back Response Time |
<1.4 s |
Ramp-Up Timer (second) |
Range |
0.0~999.9 s |
Accuracy |
± (0.1% + 0.05 sec) |
Ramp-Down Timer (second) |
Range |
0.0~999.9 s |
Accuracy |
± (0.1% + 0.05 sec) |
Delay Timer |
Range |
1 s~999.9 s / 0.1 m~999.9 min
0.1 h~999.9 h |
Accuracy |
± (0.1% + 0.1 sec) |
Dwell Timer |
Range |
0, 1s~999.9 h (0=continuous) |
Accuracy |
± (0.1% + 0.1 sec) |
Poly-phase mode (3Ø4W) for per phase measurement |
Frequency |
Range |
0.0-1000 Hz |
Resolution |
0.1 Hz |
Accuracy |
± 0.1 Hz (501-1000 Hz Accuracy ± 0.2 Hz) |
Voltage |
Range |
0.0-420.0 V |
Resolution |
0.1 V |
Accuracy |
± (0.2% of reading + 3 counts) |
Current |
Range |
L |
0.005 A~2.400 A |
H |
2.00 A~26.00 A |
Accuracy |
L |
± (1% of reading +5 counts) at 40.0-500 Hz
± (1% of reading +5 counts) at 501-1000 Hz, CF <1.5 and Current (peak) ≤7.2 A |
H |
± (1% of reading +5 counts) at 40.0-500 Hz
± (1% of reading +5 counts) at 501-1000 Hz, CF < 1.5 and Current (peak) ≤55.2 A |
Current (peak) |
Range |
0.0 A~76.0 A |
Accuracy |
± (1% of reading + 5 counts) at 40.0-70.0 Hz
± (1.5% of reading + 10 counts) at 70.1 - 500 Hz
± (1.5% of reading + 10 counts) at 501 - 1000 Hz and CF <1.5 |
Power |
Range |
L |
0.0 W~240.0 W |
H |
200 W~2600 W |
Accuracy |
L |
± (2% of reading +15 counts) at 40.0-500 Hz and PF ≥0.2
± (2% of reading +30 counts) at 501-1000 Hz and PF ≥0.5 |
H |
± (2% of reading +5 counts) at 40.0-500 Hz and PF ≥0.2
± (2% of reading +15 counts) at 501-1000 Hz and PF ≥0.5 |
Power Factor |
Range |
0 - 1.000 |
Accuracy |
W / VA, Calculated and displayed to three significant digits |
Power Apparent (VA) |
Range |
L |
0.0 VA~240.0 VA |
H |
200 VA~2600 VA |
Accuracy |
V×A, Calculated value |
Power Reactive (Q) |
Range |
L |
0.0 VAR ~ ± 240.0 VAR |
H |
0 VAR ~ ± 2600 VAR |
Accuracy |
√(VA)² - (W)², Calculated value |
Crest Factor |
Range |
0 - 10.00 |
Accuracy |
Ap / A, Calculated and displayed to two significant digits |
Poly-phase mode (3Ø4W) for Σ measurement |
Frequency |
Range |
0.0-1000.0 Hz |
Accuracy |
± 0.1 Hz (501-1000 Hz Accuracy ±0.2 Hz) |
Voltage |
Range |
0.0-727.5 V |
Calculated Formula |
(A+B+C)/√3, Calculated and displayed to one significant digits |
Current (RMS) |
Range |
L |
0.005A~2.400A |
H |
2.00A~26.00A |
Calculated Formula |
L |
∑VA/∑V |
H |
Power |
Range |
L |
0.0W~720.0W |
H |
600W~7800W |
Accuracy |
L |
A Power + B Power + C Power, Calculated value |
H |
Power Factor |
Range |
0 - 1.000 |
Resolution |
0.001 |
Accuracy |
Calculated and displayed to three significant digits |
Power Apparent (VA) |
Range |
L |
0.0VA~720.0VA |
H |
600VA~7800VA |
Calculated Formula |
L |
(∑ W ) 2 + (∑ Ǫ ) 2 |
H |
Power Reactive (Q) |
Range |
L |
0.0VAR~720.0VAR |
H |
600VAR~7800VAR |
Accuracy |
L |
A VAR + B VAR + C VAR, Calculated value |
H |
Single-phase mode (1Ø2W) Setting |
Voltage |
Range |
5.0~300 VAC, 150/300 V Auto Range |
Resolution |
0.1 V |
Accuracy |
± (0.2% of setting + 3 counts) |
Frequency |
Range |
40~1000 Hz Full Range Adjust |
Resolution |
0.1 Hz at 40.0~99.9 Hz , 1 Hz at 100~1000 Hz |
Accuracy |
± 0.03% of setting |
Starting & Ending Phase Angle |
Range |
0~359º |
Resolution |
1º |
Accuracy |
± 1º(45~65 HZ) |
Current Hi Limit |
5V~150V |
0.01~55.20 A |
5V~300V |
0.01~27.60 A |
Accuracy |
± (2.0% of setting + 2 counts) |
OC Fold Back Response Time |
< 1.4 s |
Single-phase mode (1Ø2W) measurement |
Frequency |
Range |
0.0~1000 Hz |
Accuracy |
± 0.1 Hz (501~1000 Hz Accuracy ±0.2 Hz) |
Voltage |
Range |
0.0~420.0 V |
Accuracy |
± (0.2% of reading + 3 counts) |
Current (RMS) |
Range |
0.05 A~78.00 |
Accuracy |
± (1% of reading +5 counts) at 40.0~500 Hz
± (1% of reading +5 counts) at 501~1000 Hz, CF <1.5 and Current (peak) ≤165.6 A |
Current (peak) |
Range |
0.0 A~228.0 A |
Accuracy |
± (1% of reading + 5 counts) at 40.0~70.0 Hz
± (1.5% of reading + 10 counts) at 70.1~500 Hz
± (1.5% of reading + 10 counts) at 501~1000 Hz and CF<1.5 |
Power |
Range |
0 W~7800 W |
Accuracy |
± (2% of reading +5 counts) at 40.0~500 Hz and PF ≥0.2
± (2% of reading +15 counts) at 501~1000 Hz and PF ≥0.5 |
Power Factor |
Range |
0 - 1.000 |
Accuracy |
W / VA, Calculated and displayed to three significant digits |
Power Apparent |
Range |
0 VA~7800 VA |
Accuracy |
V×A, Calculated value |
Power Reactive (Q) |
Range |
0 VAR~7800 VAR |
Accuracy |
√(VA)² - (W)², Calculated value |
Crest Factor |
Range |
0 - 10.00 |
Accuracy |
Ap / A, Calculated and displayed to two significant digits |
Poly-phase mode (1Ø3W) for per phase output setting |
Voltage |
Range |
5.0~300 VAC (phase), 10.0~600 VAC (line), 150/300 V Auto Range |
Accuracy |
± (0.2% of setting + 3 counts) |
Frequency |
Range |
40~1000 Hz Full Range Adjust |
Accuracy |
± 0.03% of setting |
Starting & Ending Phase Angle |
Range |
0~359º |
Accuracy |
± 1º(45~65 HZ) |
Current RI Limit |
5V~150V |
0.01~18.40 A |
5V~300V |
0.01~9.20 A |
Accuracy |
± (2.0% of setting + 2 counts) |
OC Fold Back Response Time |
<1.4 s |
Poly-phase mode (1Ø3W) for per phase measurement |
Frequency |
Range |
0.0-1000 Hz |
Accuracy |
± 0.1 Hz (501-1000 Hz Accuracy ±0.2 Hz) |
Voltage |
Range |
0.0-420.0 V |
Accuracy |
± (0.2% of reading + 3 counts) |
Current (RMS) |
Range |
L |
0.005 A~2.400 A |
H |
2.00 A~26.00 A |
Accuracy |
L |
± (1% of reading +5 counts) at 40.0-500 Hz
± (1% of reading +5 counts) at 501-1000 Hz, CF <1.5 and Current (peak) ≤7.2 A |
H |
± (1% of reading +5 counts) at 40.0-500 Hz
± (1% of reading +5 counts) at 501-1000 Hz, CF <1.5 and Current (peak) ≤55.2 A |
Current (peak) |
Range |
0.0 A~76.0 A |
Accuracy |
± (1% of reading + 5 counts) at 40.0-70.0 Hz
± (1.5% of reading + 10 counts) at 70.1-500 Hz
± (1.5% of reading + 10 counts) at 501-1000 Hz and CF <1.5 |
Power |
Range |
L |
0.0 W~240.0 W |
H |
200 W~2600 W |
Accuracy |
L |
± (2% of reading +15 counts) at 40.0-500 Hz and PF ≥0.2
± (2% of reading +30 counts) at 501-1000 Hz and PF ≥0.5 |
H |
± (2% of reading +5 counts) at 40.0-500 Hz and PF ≥0.2
± (2% of reading +15 counts) at 501-1000 Hz and PF ≥0.5 |
Power Factor |
Range |
0 - 1.000 |
Accuracy |
W / VA, Calculated and displayed to three significant digits |
Power Apparent (VA) |
Range |
L |
0.0 VA~240.0 VA |
H |
200 VA~2600 VA |
Accuracy |
VxA, Calculated value |
Power Reactive (Q) |
Range |
L |
0.0 VAR~240.0 VAR |
H |
0 VAR~2600 VAR |
Accuracy |
√(VA)² - (W)², Calculated value |
Crest Factor |
Range |
0-10.00 |
Accuracy |
Ap / A, Calculated and displayed to two significant digits |
Poly-phase mode (1Ø3W) for L1-L2 measurement |
Frequency |
Range |
0.0-1000.0 Hz |
Accuracy |
± 0.1 Hz (501-1000 Hz Accuracy ± 0.2 Hz) |
Voltage |
Range |
0.0-840.0V |
Accuracy |
L1 Voltage + L2 Voltage, Calculated and displayed to one significant digits |
Current (RMS) |
Range |
L |
0.005A~2.400A |
H |
2.00~26.00A |
Calculated Formula |
L |
∑VA / ∑V |
H |
Power |
Range |
L |
0.0W~480.0W |
H |
400W~5200W |
Accuracy |
L |
L1 Power + L2 Power, Calculated value |
H |
Power Factor |
Range |
0 - 1.000 |
Calculated Formula |
(L1 P + L2 P) / (L1 VA + L2 VA), Calculated and displayed to three significant digits |
Power Apparent (VA) |
Range |
L |
0.0W~480.0VA |
H |
± 400W~5200VA |
Calculated Formula |
L |
(∑ W ) 2 + (∑ Ǫ ) 2 - Calculated value |
H |
Power Reactive (Q) |
Range |
L |
0.0VAR ~ ± 480.0VAR |
H |
± 400VAR ~ ± 5200VAR |
Calculated Formula |
L |
L1 VAR + L2 VAR, Calculated value |
H |
DC OUTPUT |
Max. Power |
6000 W |
Max. Curren |
0-210 V |
28.8 A |
0-420 V |
14.4 A |
Ripple and Noise (RMS) |
Range: 5-210 V <700 mV
Range: 5-420 V <1100 mV |
Ripple and Noise (p-p) |
<4.0 Vp-p |
DC SETTINGS |
Voltage |
Range |
5-210 V / 5-420 V Selectable |
Accuracy |
± (0.2% of setting + 3 counts) |
Current Hi Limit |
5 V-210 V |
0.10 - 28.80 A |
5 V-420 V |
0.10 - 14.40 A |
Accuracy |
± (2.0% of setting + 2 counts) |
OC Fold Back Response Time |
<1.4 s |
DC MEASUREMENT |
Voltage |
Range |
0.0-420.0 V |
Accuracy |
± (0.2% of setting + 5 counts) |
Current |
Range |
0.05 A~39.00 A |
Accuracy |
± (1% of reading +5 counts) |
Power |
Range |
0 W~7800 W |
Accuracy |
± (2% of reading +5 counts) |
PROTECTION |
Software OCP |
Over Current 110% of full rated current >1 second |
Output Short Shut Down Speed |
<1 second |
Software OPP |
When over Power 105 ~ 110% of full power >5 second. When over Power >110% of full power <1 second. |
Software OTP |
Temperature over 120 degree C on the power amp and PFC heatsink |
Software OVP |
L |
When output frequency < 100Hz, maximum voltage deviation + 5V
When output frequency 101-500Hz, maximum voltage deviation + 15V
When output frequency 501-1000Hz, maximum voltage deviation + 20V |
H |
When output frequency < 100Hz, maximum voltage deviation + 10V
When output frequency 101-500Hz, maximum voltage deviation + 30V
When output frequency 501-1000Hz, maximum voltage deviation + 40V |
Software LVP |
L |
When output frequency < 100Hz, maximum voltage deviation -5V > 0.5 second
When output frequency 101-500Hz, maximum voltage deviation -15V > 0.5 second
When output frequency 501-1000Hz, maximum voltage deviation -20V > 0.5 second |
H |
When output frequency < 100Hz, maximum voltage deviation -10V > 0.5 second
When output frequency 101-500Hz, maximum voltage deviation -30V > 0.5 second
When output frequency 501-1000Hz, maximum voltage deviation -40V > 0.5 second |
Reverse Current Protection (RCP) |
Over 75W |
GENERAL |
Transient (only for 40~70 Hz) |
Trans-Volt 0.0-300.0 V Resolution 0.1 V
Trans-Site 0º~359º Resolution 1º
Trans-Time 0.5-999.9 mS Resolution 0.1 mS
Trans-Cycle 0-9999, 0-Constant |
Operation Key Feature |
Soft key, Numeric key, Rotary Knob |
Remote Input Signal |
Test, Reset, Interlock, Recall program memory 1 through 7 |
Remote Output Signal |
Pass, Fail , Test-in Process |
Key Lock |
Yes, Password Driven |
Memory |
50 memories, 9 steps/memory |
Ext Trigger |
START / END / BOTH / OFF in the Program mode, Output Signal 5 V, BNC type |
Alarm Volume Setting |
Range: 0-9 ; 0 = OFF, 1 is softest volume, 9 is loudest volume. |
Graphic Display |
240 x 64 dot resolution Monographic LCD/Contrast 9 Levels 1-9 |
PFC |
PF ≥0.97 at Full load |
Efficiency |
≥78% (at Full load) |
Auto Loop cycle |
0 = Continuous, OFF, 2~9999 |
Over Current Fold Back |
On/Off, Setting On when output current over setting Hi-A value it will fold back output voltage to keep constant output current is setting Hi-A value, Response time <1400ms |
Safety Agency |
CE Listed |
Dimensions (W x H x D) |
430 x 400.5 x 500 mm |
16.93 x 15.77 x 19.69 in |
Net Weight |
125.6 lbs (57 kg) |
Operation Environment |
0-40º/20-80% RH |