| INPUT |
310XAC |
| Phase |
1Ø |
| Voltage |
100 - 240 VAC ±10% |
| Frequency |
47 - 63 Hz |
| OUTPUT |
| Voltage |
5 - 300 V |
| Max Power |
1 kVA |
| Max Current 1Ø |
0 - 150 V |
9.2 A @ ≤110 V |
| 0 - 300 V |
4.6 A @ ≤220 V |
| Phase |
1Ø (Parallel/Poly-Phase Linking for 1Ø3W or 3Ø4W) |
| Frequency |
40.0 - 1000 Hz |
| THD |
<1% (Resistive Load) |
| Crest Factor |
Inrush CF ≥3 at 110 V, Continuous Current CF ≥3 at 110 V |
| Line Regulation |
± 0.1 V |
| Load Regulation |
± 0.5 V |
| DC OUTPUT VOLTAGE |
| Voltage |
5 - 420 V |
| Max Power |
1000 W |
| Max Current 1Ø |
0 - 210 V |
4.8 A |
| 0 - 420 V |
2.4 A |
| Ripple & Noise (Peak to Peak) |
<3.0 V |
| MEASUREMENT |
| Voltage |
Range |
0.0 - 400.0 V |
| Accuracy |
± (1% of reading + 2 counts) >5 V |
| Frequency |
Range |
0.0 - 1000 Hz |
| Accuracy |
0.0 - 500 Hz ± 0.1 Hz, 501 - 1000 Hz ± 0.2 Hz |
| Current (RMS) |
Range |
0.005 A - 13.00 A |
| Accuracy |
± (1% of reading + 5 counts) |
| Current Peak |
Range |
0.0 A - 38.0 A |
| Accuracy |
± (1% of reading + 5 counts) |
| Power |
Range |
0.0 W - 1300 W |
| Accuracy |
L |
± (2% of reading + 15 counts) at PF ≥0.2 |
| H |
± (2% of reading + 5 counts) at PF ≥0.2 |
| Power Apparent (VA) |
Range |
0.0 VA - 1300 VA |
| Calculated Formula |
V×A, Calculated value |
| Power Reactive (Q) |
Range |
0.0 VAR - 1300 VAR |
| Calculated Formula |
√(VA)²-(W)², Calculated value |
| Power Factor |
Range |
0.000 - 1.000 |
| Calculated Formula |
W/VA, Calculated and displayed to three significant digits |
| Crest Factor |
Range |
0.0 - 10.0 |
| Accuracy |
A peak / Arms, Calculated and displayed to two significant digits |
| OPTIONS |
| Grounded Neutral |
Option 2 |
All Models |
| GPIB Interface |
Option 3 |
All Models |
| 7 Remote Memory |
Option 4 |
All Models |
| Ethernet Interface |
Option 6 |
All Models |
| Linking Card |
Option 8 |
All Models |
| GENERAL |
| Operation Environment |
0 - 40ºC / 20 - 80% RH |
| Dimensions (W x H x D |
16.92 x 5.26 x 20.87 in |
| 430 x 133.5 x 530 mm |
| Net Weight |
47.16 lbs (21 kg) |
| Linking Parallel Output 1Ø2W |
| Linked Units |
2 - 3 Units, 1Ø2W (L1 - N) |
| Voltage |
Phase |
5 - 300 V |
| Power Max |
# Units |
2 |
1.8 kVA |
| 3 |
2.7 kVA |
| Max Current |
0 - 150 V |
L(2) |
14.72 A @ 20 V -110 V |
| L(3) |
22.08 A @ 20 V - 110 V |
| Line (RMS) |
0 - 300 V |
H(2) |
7.36 A @ 20 V - 220 V |
| H(3) |
11.04 A @ 20 V - 220 V |
| Linking Polyphase Output 1Ø3W |
| Linked Units |
2 Units @ 180º, 1Ø3W (L1-L2 - N) |
| Voltage |
Phase |
10 - 600 V |
| Line |
5 - 300 V |
| Power |
Max |
2 kVA |
| Max Current Phase |
0 - 300 V |
L(1) |
9.2 A @ ≤110 V |
| 0 - 600 V |
H(1) |
4.6 A @ ≤220 V |
| Max Current Line |
0 - 300 V |
L(2) |
9.2 A @ ≤220 V |
| 0 - 600 V |
H(2) |
4.6 A @ ≤440 V |
| Linking Polyphase Output 3Ø4W |
| Linked Units |
3 Units @ 120º, 3Ø4W (L1-L2-L3 - N) |
| Voltage |
Phase |
5 - 300 V |
| Line |
5 - 520 V |
| Power |
Max |
3 kVA |
| Max Current Phase |
0 - 150 V |
L(1) |
9.2 A @ ≤110 V |
| 0 - 300 V |
H(1) |
4.6 A @ ≤220 V |
| Max Current Line |
0 - 150 V |
L(3) |
9.2 A @ ≤190.5 V |
| 0 - 300 V |
H(3) |
4.6 A @ ≤381 V |
| Max Current Phase Delta |
0 - 260 V |
L(3) |
5.31 A @ ≤190.5 V |
| 0 - 520 V |
H(3) |
2.65 A @ ≤381 V |
| Linking Parallel DC Output 1Ø2W |
| Linked Units |
2 - 3 Units, 1Ø2W (L1 - N ) |
| Voltage Power |
Line |
5 - 420 V |
| Power Max |
# Units |
2 |
1.8 kVA |
| 3 |
2.7 kVA |
| Max Current |
0 - 210 V |
L(2) |
7.68 A @ 50 V - 210 V |
| L(3) |
11.52 A @ 50 V - 210 V |
| Line |
0 - 420 V |
H(2) |
3.84 A @ 50 V - 420 V |
| H(3) |
5.76 A @ 50 V - 420 V |
| Measurement (Total) Linking Parallel 1Ø2W |
| Voltage |
Range |
0.0 - 400.0 V |
| Accuracy |
± (1% of reading + 2 counts) >5 V |
| Frequency |
Range |
0.0 - 1000.0 Hz |
| Accuracy |
L |
± 0.1 Hz @ 0.0 - 500 Hz |
| H |
± 0.2 Hz @ 501 - 1000 Hz |
| Current (RMS) |
Range |
2 |
0.00 A - 26.00 A |
| 3 |
0.00 A - 39.00 A |
| Accuracy |
L |
± (1.5% of reading +15 counts) x # of Linked Units / @ 40.0 - 70.0 Hz & Current is >1.0 A |
| H |
± (1.5% of reading +15 counts) x # of Linked Units / @ 70.1- 1000 Hz & Current is >5.00 A |
| Power (W) |
Range |
2 |
0 W - 2600 W |
| 3 |
0 W - 3900 W |
| Accuracy |
± (2% of reading + 10 counts) x (# of Linked Units) at PF ≥0.2, 40 - 500 Hz, and Current >5.0 A
± (2% of reading + 10 counts) x (# of Linked Units) at PF ≥0.3, 501 - 1000 Hz, and Current >5.0 A |
| Power Apparent (VA) |
Range |
2 |
0 W - 2600 VA |
| 3 |
0 W - 3900 VA |
| Accuracy |
V x A, Calculated Value |
| Power Reactive (Q) |
Range |
2 |
0 W - 2600 VA |
| 3 |
0 W - 3900 VA |
| Accuracy |
√(VA)² - (W)², Calculated Value |
| Power Factor |
Range |
0 - 1.000 |
| Accuracy |
W / VA, Calculated and displayed to three significant digits |
| Measurement (Total) Linking Polyphase 1Ø3W |
| Voltage |
Range |
2 |
L1 Voltage + L2 Voltage |
| Accuracy |
Summation of linked sources, Calculated and displayed to one significant digit |
| Frequency |
Range |
0.0 - 1000.0 Hz |
| Accuracy |
L |
± 0.1 Hz @ 0.0 - 500 Hz |
| H |
± 0.2 Hz @ 501 - 1000 Hz |
| Current (RMS) |
Range |
2 |
(L1 Current + L2 Current)/2 |
| Accuracy |
± (1% of reading + 5 counts) at 40 - 70 Hz
± (1% of reading + 5 counts) at 70.1 - 500 Hz, and output current (RMS) >0.200 A
± (1% of reading + 5 counts) at 501 - 1000 Hz, and output current (RMS) >0.300 A |
| Power (W) |
Range |
2 |
L1 Power + L2 Power |
| Accuracy |
2 |
L1 Power + L2 Power, Calculated Value |
| Power Apparent A) |
Range |
2 |
L1 VA + L2 VA |
| Accuracy |
2 |
L1 VA + L2 VA, Calculated Value |
| Power Reactive (Q) |
Range |
2 |
L1 VAR + L2 VAR |
| Accuracy |
2 |
L1 VAR + L2 VAR, Calculated Value |
| Power Factor |
Range |
0 - 1.000 |
| Accuracy |
(L1 P + L2 P) / (L1 VA + L2 VA), Calculated and displayed to three significant digits |
| Measurement (Total) Linking Polyphase 3Ø4W |
| Voltage |
Range |
(A+B+C)/3 |
| Accuracy |
(A+B+C)/3, Calculated and displayed to one significant digit |
| Frequency |
Range |
0.0 - 1000.0 Hz |
| Accuracy |
L |
± 0.1 Hz @ 0.0 - 500 Hz |
| H |
± 0.2 Hz @ 501 - 1000 Hz |
| Current (RMS) |
Range |
(A+B+C)/3 |
| Accuracy |
± (1% of reading + 5 counts) at 40 - 70 Hz
± (1% of reading + 5 counts) at 70.1 - 500 Hz, and output current (RMS) >0.200 A
± (1% of reading + 5 counts) at 501 - 1000 Hz, and output current (RMS) >0.300 A |
| Power (W) |
Range |
A Power + B Power + C Power |
| Accuracy |
Calculated Value |
| Power Apparent (VA) |
Range |
A VA + B VA + C VA |
| Accuracy |
Calculated Value |
| Power Reactive (Q) |
Range |
A VAR + B VAR + C VAR |
| Accuracy |
Calculated Value |
| Power Factor |
Range |
0 - 1.000 |
| Accuracy |
Sum P / Sum VA, Calculated and displayed to three significant digits |
| Measurement (Total) Linking Parallel DC |
| Voltage |
Range |
0.0 - 420.0 V |
| Accuracy |
± (1% of reading + 2 counts) >5 V |
| Current (RMS) |
Range |
2 |
0.05 A - 26.00 A |
| 3 |
0.05 A - 39.00 A |
| Accuracy |
± (1% of reading + 5 counts) x # of Linked Units, Current >1.00 A |
| Power (W) |
Range |
2 |
0 W - 2600 W |
| 3 |
0 W - 3900 W |
| Accuracy |
± (2% of reading + 5 counts) x # of Linked Units |