Technical parameters |
Value |
Output |
Ethernet |
Measured Value |
Temperature + Relative Humidity + Atmospheric Pressure |
Construction Type |
With T+RH Probe on Cable |
Design |
Industrial |
Temperature Measuring |
Range -30 to 80 °C |
Relay Output |
No |
Two-State Input |
No |
Lcd Display |
Yes |
PoE |
No |
Relative humidity range |
0 to 100% |
Accuracy of relative humidity measurement |
±2.5% relative humidity from 5 to 95% at 23°C |
Accuracy of temperature output |
±0.6°C |
Maximum measuring atmospheric pressure range |
600 to 1100hPa |
Accuracy of atmospheric pressure |
±1.3hPa at 23°C |
Resolution |
0.1°C, 0.1%RH, 0.1hPa |
Measuring interval |
2s |
Available temperature units |
degrees Celsius, degrees Fahrenheit |
Computed values |
dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy |
Available atmospheric pressure units |
hPa, kPa, mBar, mmHg, inHg, inH2O, PSI, oz/in2 |
Accuracy and range of dew point temperature output - for more details see graphs in manual |
±1.5°C at ambient temperature T<25°C and RH>30% range -60 to +80°C |
Range of humidity sensor temperature compensation |
all temperature range |
Temperature operating range of case with electronics |
-30 to +80°C |
IP protection |
IP30 electronics, IP40 sensors |
LAN connection |
RJ-45 connector, 10Base-T or 100Base-TX |
Communication protocols |
WWW, ModbusTCP, SNMPv1, SOAP, XML |
Alarm protocols |
E-mail, SNMP Trap, Syslog |
Configuration |
T-Sensor, WWW configuration |
Power |
9 to 30Vdc, maximum consumption 1W |
Power connector |
co-axial, diameter 5.5 x 2.1mm |
Dimensions |
88.5 x 147.5 x 39.5mm (W x H x D), stem length 75mm |
Weight |
approximately 155g |
Warranty |
3 years |