| Comet T3419P Specification |
| Technical parameters |
Value |
| Output |
RS485 |
| Measured Value |
Temperature + Relative Humidity |
| Construction Type |
Compressed Air Humidity up to 2.5MPa |
| Design |
Industrial |
| Temperature Measuring Range |
-30 to 105 °C |
| Relay Output |
No |
| Two-State Input |
No |
| Lcd Display |
Yes |
| PoE |
No |
| Relative humidity range |
0 to 100% |
| Accuracy of relative humidity measurement |
±2.5% relative humidity from 5 to 95% at 23°C |
| Accuracy of temperature output |
±0.4°C from -30 to +100°C ±0.4% from reading over +100°C |
| Available temperature units |
degrees Celsius, Fahrenheit |
| Dew point temperature range |
-60 to +80 °C |
| Accuracy of dew point temperature output (for more details see instruction manual) |
±1.5°C for dew point temperature +10°C and higher at ambient temperature +25°C |
| Accuracy of dew point temperature output |
±2.0°C for dew point temperature 0°C at ambient temperature +25°C |
| Accuracy of dew point temperature output |
±3.0°C for dew point temperature -10°C at ambient temperature +25°C |
| Accuracy of dew point temperature output |
±6.0°C for dew point temperature -20°C at ambient temperature +25°C |
| Accuracy and range of absolute humidity output |
±1.5g/m3 at ambient temperature T < 25°C range 0 to 400 g/m3 |
| Accuracy and range of specific humidity output |
±2g/kg at ambient temperature T < 35°C range 0 to 550 g/kg |
| Accuracy and range of mixing ratio output |
±2g/kg at ambient temperature T < 35°C range 0 to 995 g/kg |
| Accuracy and range of specific enthalpy output |
±3kJ/kg at ambient temperature T < 25°C range: 0 to 995 kJ/kg |
| Temperature operating range of case with electronics |
-30 to +80°C |
| Temperature operating range of LCD display |
readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C |
| Range of humidity sensor temperature compensation |
all temperature range |
| Communication protocol |
ModBus RTU and Advantech ADAM compatible protocol |
| Communication speed |
110 to 115200 Bd |
| Filtering ability of sensor cover |
0.025mm - filter with stainless steel mesh |
| Protection of the case with electronics |
IP65 electronics, IP40 sensors |
| Power |
9-30Vdc, current consumption approximately 0.5W |
| Mechanical connection of probe |
G1/2 with O-Ring |
| Length of the probe cable |
1m, 2m or 4m optionally |
| Dimensions |
display unit 88.5 x 114 x 39.5 mm (W x H x D), probe length 150 mm, probe diameter 18mm |
| Weight |
approximately 260g - 1m probe |
| Warranty |
3 years |