Refrigerant Library |
R-11, R-12, R-21, R-22, R-23, R-113, R-114, R-123, R-124, R-134a, R-227, R-236FA, R-401a, R-402a, R-402b, R-404a, R-407a, R-407c, R-408a, R-409a, R-410a, R-500, R-502, R-503, R-507, R-508b, H-1211, H-1301, H-2404, N-1230 |
Measuring Range |
All gases 0 to 10,000 ppm |
Input |
Dedicated single zone |
Output Signals |
4 SPDT, 5 Amp, 240 VAC relays; digital display; and a 4?20 mA DC current loop output |
Detector Type |
Single pass, non-dispersive infrared |
Sensitivity |
All gases 1 ppm |
Accuracy |
All gases ±10 ppm from 0 to 100 ppm, ±10% of reading from 100 to 10,000 ppm |
Front Panel Indicators |
MONITOR ON - Green light ON when the unit is operating normally, or flashing during warm-up
SYSTEM FAULT - Yellow light ON when there is a system fault
ALARM - Red light ON when the gas level is above an alarm setting |
Response Time |
9 to 30 seconds, depending on tube length and gas concentration |
Max. Monitoring Distance |
Up to 50 feet from measuring point to monitor |
Operating Temperature |
32 to 122°F (0 to 50°C) |
Humidity |
5 to 90% RH, non-condensing |
Altitude Limit |
2000 Meters |
Power |
100-240 VAC, 50/60 Hz, 15 Watts |
Size/Weight |
14"H x 18"W x 4.7"D / 7 lbs |
Certification |
UL 61010A-1, CSA 22.2, CE Mark |