Analog Output (4-20mA) |
Accuracy |
± 1.0% FS (Accuracy includes the effects of linearity, hysteresis, repeatability, zero offset and span setting errors) |
Response Time |
30msec–10sec (by user) |
Output Resolution |
±0.05% FS |
Analog Scaling |
User may configure analog output scaling to any range within −100 to +150% Full Scale of the sensor range |
Pressure Switch Output |
Type |
NPN or PNP open collector up to 80ma |
Setting Accuracy |
± 1.0% FS |
Response Time |
5msec – 10.0 sec (by user) |
Hysteresis |
Variable (by user) |
Switch Setting |
User may adjust switch actuation & deadband to any points within Full Scale sensor range |
Display |
Type |
4 digit, 8mm LED |
Accuracy |
± 1.0% FS (URL) + last digit |
Display Update Rate |
200msec−10.0 sec (by user) |
Display Setting |
User may re-configure display scaling, set to capture MIN or MAX value and adjust display update rate |
Standard Ranges (Gauge) |
0 to 50 psig, 100 psig, 150 psig, 300 psig, 500 psig, 1000 psig, 1500 psig, 3000 psig, 5000 psig, 7500 psig |
Standard Ranges (Compound) |
-15 to 75 psig, -15 to 150 psig -15 to 300 psig, |
ENVIRONMENTAL SPECIFICATIONS |
Temperature Limits |
Storage |
-20 to 70°C (-4 to 158°F) |
Operating |
-20 to 70°C (-4 to 158°F) |
Compensated |
-20 to 70°C (-4 to 158°F) |
Temperature Effects |
Zero/Span |
±0.1%FS/°C (from 23°C reference temp.) |
Humidity |
0-85% RH (Ranges 150 psi & below)
0-100% RH (Ranges 300 psi & above) |
FUNCTIONAL SPECIFICATIONS |
Proof Pressure |
4X Range (ranges 1500 psi & below)
2.5X Range (ranges 3000 psi & above) |
Burst Pressure |
10X Range (ranges 1500 psi & below)
5X Range (ranges 3000 psi & below)
3X Range (ranges 5000 psi & above) |
Withstand Voltage |
350Vac 1 minute |
Insulation Voltage |
50 Vdc 100MΩmin |
CE Compliance |
EN61326-1: 2006, EN61326-2-3: 2006
EU RoHS Compliance |
Stability |
±0.25% FS/year |
ELECTRICAL SPECIFICATIONS |
Power Supply Requirements |
Supply Voltage |
16-36Vdc (with analog output option)
11-36Vdc (switch output version only) |
Current Consumption |
50mAdc max |
Switch Contacts |
User selectable NPN or PNP open collector outputs |
NPN Type |
30Vdc / 80mA (max) |
PNP Type |
Supply Voltage 80mA (max)
Voltage Drop 1Vdc (max) |
MECHANICAL SPECIFICATIONS |
Pressure Connection |
1⁄4 NPT (Male) |
Connection Location |
Lower, back |
Enclosure |
Nickel plated aluminum |
Rating |
IP65 (ranges 150 psi and below)
IP67 (ranges 300 psi and above) |
Electrical Connection |
M12 connector (4 pin) |
Weight |
Approx. 150 grams |
Media |
Fluids and gases compatible with 316SS
(sensor housing) and 17-4 pH SS (sensor diaphragm) |