AEMC 2113.75 Specifications |
Electrical Specifications |
Number Of Channels |
1 |
Measurement Range |
5 to 500Arms, 5 to 5000Arms |
Input |
5 to 500 or 5 to 5000Arms, Internally Switch Selectable |
Input Sensor |
AmpFlex™ 36" Flexible Current Probe |
Input Connections |
Permanent Flexible Sensor |
Resolution |
500A range: 2A max, 5000A range: 20A max |
Resolution |
Scale Range |
100% / 50% / 25% / 12.5% |
Max Input |
500Arms / 250Arms / 125Arms / 62.5Arms |
Resolution |
2Arms / 1Arms / 0.5Arms / 0.25Arms |
Accuracy |
1% of Reading + Resolution |
Sample Rate |
4096/hr maximum |
Data Storage |
8192 readings |
Data Storage Technique |
Time Extension Recording™ (TXR™) |
Power Source |
9V Alkaline battery |
Battery Life |
Up tp 6 months of recording @ 25° C |
Output |
RS-232 via DB9 connector |
Indicators |
Red LED double flashes in LOGGING, single flashes in STANDBY, and is off in OFF mode |
Controls |
One button is used to start and stop recording sessions and to turn the data logger on and off |
Select Switch |
Internal range selector slide switch |
Working Voltage |
600VAC |
Mechanical Specifications |
Size |
Sensor: Diameter 0.5" (12.5mm), Logging Module: 1-9/16x2-1/2x4-1/2 (40.64x63.5x114.3) |
Weight |
15.5oz |
Max Conductor Size |
24" length: 8" diameter conductor |
Mounting |
Velcro pads supplied loose |
Environmental Specification |
Operating Temperature |
-4° to +158°F (-20° to +70°C) |
Storage Temperature |
-40° to +174°F (-40° to + 80°C) |
Relative Humidity |
5 to 95% non-condensing |
Protection Index |
NEMA4X / IP56 |
Software Compatibility |
Windows 3.1, Windows 95, Windows 98 |
Safety Reference Specifications |
Safety Rating |
IEC 1010, 600V, Cat. III |