| AEMC 1431.01 Specifications |
| Electrical Specifications |
| Power Source |
Rechargeable 6V, 7Ah NiCad battery, built-in 110/220V (47 - 450Hz) charger; automatic shutoff after |
| Battery Life |
2000µW range: 200 to 300 8-second measurements; 20-200mW ranges: 900 30-second measurements; 2000mW, 20-200W ranges: 5000 30-second measurements |
| Operating Voltage |
4.5 - 7VDC |
| Recharge Time |
14 hours from full discharge |
| Recharge Time |
| Range |
2000µW / 20mW / 200mW / 2000mW / 20W / 200W |
| Display |
1999 / 19.99 / 199.9 / 199 / 19.99 / 199.9 |
| Resolution |
1µW / 10µW / 100µW / 1µW / 10µW / 100µW |
| Test Current |
10A / 1A / 100mA / 10mA |
| Accuracy |
0.25% of Reading, 0.5% max ±2 digits / 0.25% of Reading, 0.5% max ±1 digit |
| Mechanical Specifications |
| Display |
2000 count, 7-segment LED |
| Case |
Fiberglass-charged polycarbonate, with handle and removable lid, watertight to IP534 (lid closed), IP520 (lid open); UL94 |
| Color |
Safety yellow case with gray face plate |
| Fuses |
Two high interrupting capacity, 8A, 380V, 1-1/4" x 1/4" |
| Dimensions |
15.35 x 10.24 x 9.84" (390 x 260 x 250mm) |
| Weight |
17lbs (8kg) |
| Environmental Specification |
| Operating Temperature |
14° to 131°F (-10° to 55°C) |
| Storage Temperature |
-4° to 131°F (-20°C to 55°C) |
| Dielectric Test |
IEC348, 1500V 60Hz (input terminals) 3000V 60Hz (power supply) |
| Overload Input Protection |
380Vrms |
| Safety Reference Specifications |
| Safety Ratings |
IEC348, Class II; IEC38; IEC801-2; IEC801-3; IEC801-5; IEC529; IEC68.2.6; IEC68.2.27; IEC68.2.29; IEC68.2.31; IEC68.2.32 |
| Agency Approvals |
CE Mark |