AEMC 2113.29 Specifications |
Electrical Specifications |
Measurement Range |
5 to 10,000A |
Output Signal |
1mV/A & 0.1mV/A |
Accuracy |
1% of Reading |
Crest Factor |
9 |
Phase Shift @ 50/60Hz |
0.5° |
Frequency Range |
10 to 20,000Hz (intentionally limited for optimum performance) |
Residual Noise |
1A |
Working Voltage |
1000Vrms max. |
Influence of Frequency |
Add 1% to the reference |
Influence of Adjacent Conductor |
<2% |
Influence of Conductor Position in Jaw |
<4% |
Mechanical Specifications |
Output |
Two 4mm safety banana jacks, standard 3/4" (19mm) spacing |
Battery |
9V Alkaline |
Low Battery |
Green LED Off when ³ 7V |
Overload Indication |
Red LED indicates input greater than selected range |
Battery Life |
150 hours typical (continuous use) |
Sensor Dimensions |
60" |
Electronic Module Dimensions |
4.9 x 2.5 x 1.1" (124 x 64 x 28mm) |
Cable Length |
6.5ft (2m) |
Drop Test |
1.0m on 38mm of oak or concrete. Test according to IEC1010 |
Vibration |
Test per IEC 68-2-6, Frequency Range: 10Hz to 55Hz, Amplitude: 0.15mm |
Mechanical Shock |
100G, Test per IEC 68-2-32 |
Environmental Specification |
Case Protection |
Sensor: IP65 per IEC529; Electronic Module: IP40 |
Operating Temperature |
14 to 131°F (-10°C to +55°C) |
Storage Temperature |
-40 to 158°F (40°C to +70°C) |
Influence of Temperature |
Sensor: -10°C to 100°C: <0.5% per 10°C; Module: -10°C to 55°C: <0.5% per 10°C |
Operative Relative Humidity |
10 - 30°C 85 ±5% RH without condensation; 40 - 50°C 45 ±5% RH (without condensation) |
Altitude |
Operating: 0 to 2000m; non-operating: 0 to 12000m |
Safety Reference Specifications |
Safety Ratings |
EN 61010, 1000V, Cat. III, Pollution Degree 2 |
Agency Approvals |
CE Mark |